Page | 41
MINT – IO
REF NO: m25A/om/101
Issue No: 11
4.3.4 Wiring Diagram:
The following diagram shows how the Analog Inputs are connected to the
Input Terminals.
*
50 ohms
Connected
Outside
4.3.5 Modbus Address for configuration:
Parameter
Address
Description
Process Value (INT)
1
30001
– 30008 Channel 1 – 8 Inputs – Read Only
Process Value (Swap Float)
1
30051
– 30065 Channel 1 – 8 Inputs – Read Only
Ambient Temperature (INT)
30009
Ambient Temperature Read Only
Ambient Temperature (Swap Float)
30067
Ambient Temperature Read Only
Input Types
2
40001
– 40008 Channel 1 – 8 Input Types
User Zero Range
40073
– 40080 Channel 1 – 8 Input User Zero
User Span Range
40097
– 40104 Channel 1 – 8 Input User Span
Calibration Ambient
(Password Protected)
- Factory Use
40249
Ambient Temperature Calibration
(
0
°C
– 55.0°C)
Decimal Points for Floating Values
(only for Voltage & Current Inputs)
40121-40128
0
-xxxxx,
1
-xxxx.x,
2
-xxx.xx
3
-xx.xxx,
4
-x.xxxx,
5
-0.xxxxx
* Calibration is used for factory purpose, these parameters are not recommended to use on field.
Type
Description
Resolution Accuracy Type
Description
Resolution Accuracy
E - Type TC
0.1°C
+/-
0.5°C
Pt-100 3W
0.1°C
+/-
1°C
J - Type TC
0.1°C
+/-
0.5°C
CU-53
0.1°C
+/-
1°C
K - Type TC
0.1°C
+/-
0.5°C
NI 120
0.1°C
+/-
1°C
T - Type TC
0.1°C
+/-
0.5°C
resistance
1
Ω
+/-
0.01%
B - Type TC
1°C
+/-
1°C
R - Type TC
1°C
+/-
1°C
Current
1uA
+/-
0.05%
S - Type TC
1°C
+/-
1°C
Voltage (mV)
0.1mV
+/-
0.01 %
N - Type TC
1°C
+/-
1°C
Voltage (V)
1mV
+/-
0.01 %