2.5.1 Communications Settings with DIP Switch 8 ON (Default):
Baud rate : 9600
Parity : None
Data length : 8
Stop bits : 1
2.5.2 Communications Settings with DIP Switch 8 OFF(Programmed
Baud Rate):
Baud rate : 9600, 19200, 38400, 57600, 115200
Parity : None, even, odd
Data length : 8
Stop bits : 1, 2
These communication settings are done from mINT configuration software or
any MODBUS Master software. After changing these parameters, Module
must restart to take the effect of changed parameter.
2.5.3 Communications Settings Registers
Address
Parameter
Min
value
Max
Value
Description
COM1
42001
Slave ID
1
127
Read Only Parameter
42002
Baud rate
1
5
1 = 9600,
2 = 19200,
3 = 38400,
4 = 57600,
5 = 115200
42003
Parity
0
2
0 = None,
1 = Even,
2 = Odd
42004
Stop Bits
1
2
1 = 1 Stop bit,
2 = 2 Stop bits
42005
Data Length
8
8
8 = 8 Data Bits
COM2
42006
Slave ID
1
127
Read Only Parameter
42007
Baud rate
1
5
1 = 9600,
2 = 19200,
3 = 38400,
4 = 57600,
5 = 115200
42008
Parity
0
2
0 = None,
1 = Even,
2 = Odd
42009
Stop Bits
1
2
1 = 1 Stop bit,
2 = 2 Stop bits
42010
Data Length
8
8
8 = 8 Data Bits