7 ANOMALIES, CAUSES AND REMEDIES
7.1 Breackdown table
The starter motor turns but the main engine does not start
- Check that the stop solenoid valve is powered.
(Consult Service Centre).
- Perform operations of drainage from air beads inside the fuel circuit
The engine protection module is not activated pressing the pulsating START
- Check if the thermal interrupter of protection is open.
(To restore the contact pressing on the button)
.
- Check the cables and the clamps of connection to the battery and the electric connections.
(Reconnect)
.
- Check the integrity of the battery.
(Reload or Replace)
.
The generator switches off during the operating period
- Check if a protection has been activated.
(Solve the problem and restart)
.
- Check if there is fuel in the tank.
(Fill up)
.
There is high smoke emission from the exhaust.
- Check that the oil level does not exceed the
MAX
level.
(Bring it down to the correct level)
.
- Check the generator group is not overloaded.
- Check the injectors.
(Consult Service Centre).
The engine runs irregularly
- Check the fluel filter.
(Replace it)
- Perform operations of drainage from air beads inside the fluel circuit.
@
The tension of the alternator is too much low.
- Correct the value of the tension adjusting the electronic regulator.
- Check the rpms motor
(3120 rpms without connected uses)
.
- Voltage regulator failure
(Replace)
.
The generator has no power at the outlets.
- Check if the magnetothermal switch is in
ON
position (consult Service Centre).