background image

8

Safety 

Precautions

Page 8 

7.

Repairs to sealed components

:

1)

During repairs to sealed components, all electrical supplies shall be disconnected from the equipment

 The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure 
   the technician is aware of potentially flammable atmospheres. Ensure that the leak detection 
   equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately 
   sealed or intrinsically safe.

5)

Presence of fire extinguisher

:

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate

 

fire

extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher

 

adjacent

to the charging area.

6)

No ignition sources

:

No person carrying out work in relation to a refrigeration system which involves exposing any pipe
work that contains or has contained flammable refrigerant shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site of installation, repairing, removing and
disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior
to work taking place, the area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. No Smoking signs shall be displayed.

7)

Ventilated area

:

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or
conducting any hot work. A degree of ventilation shall continue during the period that the work is carried
out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into
the atmosphere.

8)

Checks to the refrigeration equipment

:

Where electrical components are being changed, they shall be fit for the purpose and to the correct
specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in
doubt consult the manufacturer's technical department for assistance. The following checks shall be
applied to installations using flammable refrigerants:
The charge size is in accordance with the room size within which the refrigerant containing parts are
installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence

 

of

refrigerant; Marking 

on

 the equipment continues to be visible and legible. Markings and signs that

 

are

illegible shall be corrected;
Refrigeration pipe or components are installed in a position where they are unlikely to be exposed
to any substance which may corrode refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to  being corroded or are suitably protected
against being so corroded.

9)

Checks to electrical devices

:

Repair and maintenance to electrical components shall include initial safety checks and component
inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be
connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately

 

but

it is necessary to continue operation, an adequate temporary solution shall be used. This shall be

 

reported

to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
That there no live electrical components and wiring are exposed while charging, recovering or purging
the system; That there is continuity of earth bonding.

Summary of Contents for Comfort-Aire PS-121C

Page 1: ...www marsdelivers com Owner s Manual Installation Manual Portable Air Conditioner PS 121C PSH 141C...

Page 2: ...recautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaus...

Page 3: ...d on the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and v...

Page 4: ...he appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the supply power cord is damaged it must be replaced by the man...

Page 5: ...tact a qualified person to carry out repairs If the damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and not repaired Hold the plug by the...

Page 6: ...ce of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Please follow the instructions carefully to handle install clear a...

Page 7: ...system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General work are...

Page 8: ...into the atmosphere 8 Checks to the refrigeration equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufactur...

Page 9: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the s...

Page 10: ...actice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant...

Page 11: ...ly Installation Instructions Preparation NOTE All the illustrations in the manual are for explanation purpose only Your machine may be slightly different The actual shape shall prevail The unit can be...

Page 12: ...damage to the unit 50cm 19 7 inch 30cm 30cm 12inch 12inch 50cm 19 7inch Energy Rating Information The energy rating and noise information for this unit is based on the standard installation using an...

Page 13: ...aving the air feeling damp To find the proper air conditioner determine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air condit...

Page 14: ...lider A Bolt 1 pc 1 set Unit Adaptor Security Bracket and 2 Screws 1 pc 1 pc Exhaust Hose Drain Hose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T...

Page 15: ...e Adjustable Window Slider or or Window slider A MODEL A MODEL B Window slider B Bolt Window slider A Window slider B Bolt MODEL A MODEL B MODEL C MODEL D 1 2 Window slider A Window slider B Window sl...

Page 16: ...em to the window sash and frame as shown 2 Insert the window slider assembly into the window opening Or Foam seal B Adhesive type shorter Foam seal A Adhesive type Foam seal B Adhesive type shorter Fo...

Page 17: ...wall for the Wall Exhaust Adapter B 2 Secure the Wall Exhaust Adapter B to the wall using the four Anchors and Screws provided in the kit 3 Connect the Exhaust Hose Assembly with Wall Exhaust Adapter...

Page 18: ...s light within 8 minutes the unit will exit Wireless connection mode automatically and the Wireless indicator illuminates If connection has failed within 8 minutes the unit exits Wireless connection m...

Page 19: ...tion When the function is turned on the constant fan light will illuminate identifying the fan continuous run for cooling When the function is turned off the constant fan light will go out identifying...

Page 20: ...he Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time...

Page 21: ...hout drain connector just attach the drain hose to the hole Place the open end of the Hose adaptor directly over the drain area in your basement floor that there are no kinks that will stop the water...

Page 22: ...unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the appliance on FAN mode for 12 hours in a warm room to dry it and pr...

Page 23: ...Decrease the set temperature Make sure all windows and doors are closed Double check the cooling area Turn off the unit disconnect the hose check for blockage and reconnect the hose Remove the heat so...

Page 24: ...warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY The sole remedy under the Limited Warranty is replacement of the defective unit Labor to diagno...

Page 25: ...GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEO...

Reviews: