background image

10

Safety 

Precautions

Page 10

15.

Labeling

:

Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The
label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment
contains flammable refrigerant.

16.

Recovery

:

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders,
ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct
number of cylinders for holding the total system charge is available. All cylinders to be used are
designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the
recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before

13.

Charging procedures

:

In addition to conventional charging procedures, the following requirements shall be followed. Ensure

 

that contamination of different refrigerants does not occur when using charging equipment. Hoses or

 

lines shall be as short as possible to 

minimize

 the amount of refrigerant contained in them.

Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it

 

shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior

 

to commissioning. A follow up leak test shall be carried out prior to leaving the site.

14.

Decommissioning

:

Before carrying out this procedure, it is essential that the technician is completely familiar with the

 

equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely.

 

Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is

 

required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before

 

the task is commenced.

15.

Become familiar with the equipment and its operation.    b) Isolate system electrically.    c) Before

 

attempting the procedure ensure that: Mechanical handling equipment is available, if required, for

 

handling refrigerant cylinders;All personal protective equipment is available and being used correctly;

 

The recovery process is supervised at all times by a competent person; Recovery equipment and

 

cylinders conform to the appropriate standards.    d) Pump down refrigerant system, if possible.    e) If a

 

vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of  the

 

system.     f) Make sure that cylinder is situated on the scales before recovery takes place.    g) Start the

 

recovery machine and operate in accordance with manufacturer's instructions.    h) Do not overfill

 

cylinders. (No more than 80 % volume liquid charge).     i)  Do not exceed the maximum working

 

pressure of the

 

cylinder, even temporarily.     j)  When the cylinders have been filled correctly and the

 

process completed, make sure that the cylinders and the equipment are removed from site promptly

 

and all isolation valves on the equipment are closed off.     k) Recovered refrigerant shall not be charged

 

into another refrigeration  system unless it has been cleaned and checked.

oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system 
with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. 
When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable 
work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take 
place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is 
ventilation available.

Summary of Contents for Comfort-Aire PS-121C

Page 1: ...www marsdelivers com Owner s Manual Installation Manual Portable Air Conditioner PS 121C PSH 141C...

Page 2: ...recautions Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaus...

Page 3: ...d on the nameplate located on unit have a qualified electrician install the proper receptacle Install the unit on a flat sturdy surface Failure to do so could result in damage or excessive noise and v...

Page 4: ...he appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the supply power cord is damaged it must be replaced by the man...

Page 5: ...tact a qualified person to carry out repairs If the damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and not repaired Hold the plug by the...

Page 6: ...ce of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants Please follow the instructions carefully to handle install clear a...

Page 7: ...system 2 Work procedure Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed 3 General work are...

Page 8: ...into the atmosphere 8 Checks to the refrigeration equipment Where electrical components are being changed they shall be fit for the purpose and to the correct specification At all times the manufactur...

Page 9: ...copper pipe work If a leak is suspected all naked flames shall be removed extinguished If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the s...

Page 10: ...actice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant...

Page 11: ...ly Installation Instructions Preparation NOTE All the illustrations in the manual are for explanation purpose only Your machine may be slightly different The actual shape shall prevail The unit can be...

Page 12: ...damage to the unit 50cm 19 7 inch 30cm 30cm 12inch 12inch 50cm 19 7inch Energy Rating Information The energy rating and noise information for this unit is based on the standard installation using an...

Page 13: ...aving the air feeling damp To find the proper air conditioner determine the square footage of the room you want to cool by multiplying the room length by its width You also need to know the air condit...

Page 14: ...lider A Bolt 1 pc 1 set Unit Adaptor Security Bracket and 2 Screws 1 pc 1 pc Exhaust Hose Drain Hose 1 pc 1 pc Window Slider Adaptor Power Cord Buckle O N O F F T E M P S H O R T C U T T IM E R O N T...

Page 15: ...e Adjustable Window Slider or or Window slider A MODEL A MODEL B Window slider B Bolt Window slider A Window slider B Bolt MODEL A MODEL B MODEL C MODEL D 1 2 Window slider A Window slider B Window sl...

Page 16: ...em to the window sash and frame as shown 2 Insert the window slider assembly into the window opening Or Foam seal B Adhesive type shorter Foam seal A Adhesive type Foam seal B Adhesive type shorter Fo...

Page 17: ...wall for the Wall Exhaust Adapter B 2 Secure the Wall Exhaust Adapter B to the wall using the four Anchors and Screws provided in the kit 3 Connect the Exhaust Hose Assembly with Wall Exhaust Adapter...

Page 18: ...s light within 8 minutes the unit will exit Wireless connection mode automatically and the Wireless indicator illuminates If connection has failed within 8 minutes the unit exits Wireless connection m...

Page 19: ...tion When the function is turned on the constant fan light will illuminate identifying the fan continuous run for cooling When the function is turned off the constant fan light will go out identifying...

Page 20: ...he Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time...

Page 21: ...hout drain connector just attach the drain hose to the hole Place the open end of the Hose adaptor directly over the drain area in your basement floor that there are no kinks that will stop the water...

Page 22: ...unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the appliance on FAN mode for 12 hours in a warm room to dry it and pr...

Page 23: ...Decrease the set temperature Make sure all windows and doors are closed Double check the cooling area Turn off the unit disconnect the hose check for blockage and reconnect the hose Remove the heat so...

Page 24: ...warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY The sole remedy under the Limited Warranty is replacement of the defective unit Labor to diagno...

Page 25: ...GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEO...

Reviews: