![MARS COMMERCE SOLO-NX Instruction Manual Download Page 9](http://html1.mh-extra.com/html/mars-commerce/solo-nx/solo-nx_instruction-manual_1730649009.webp)
SOLO-NX
INSTALLATION MANUAL
Page 9
9.1.1.4
Table of parameters
Name
Comment
IN1
Mode of operation for input 1
IN2
Mode of operation for input 2
IN3
Mode of operation for input 3
IN4
Mode of operation for input 4
ID1
Input time integration delay on input 1
ID2
Input time integration delay on input 2
ID3
Input time integration delay on input 3
ID4
Input time integration delay on input 4
DD1
Time delay for alarm reporting on input 1
DD2
Time delay for alarm reporting on input 2
DD3
Time delay for alarm reporting on input 3
DD4
Time delay for alarm reporting on input 4
Table 1: IN, ID and DD parameters
Example:
Direct programming on the SIM card
SOLO-NX PROGRAMMING TABLE
SIM CARD PHONE BOOK
Name
Number
Description
IN1
0
Alarm activated by connecting to GND
IN2
4
Alarm activated by connecting to GND + RST SMS
ID1
10
Input 1 has to be valid for 10 second to trigger the alarm
ID2
0
Input 2 has to be valid for 0,5 second to trigger the alarm
DD1
0
Reporting of the alarm on input 1 is delayed by 0s
DD2
15
Reporting of the alarm on input 1 is delayed by 15s
Table 2: IN, ID, DD parameters example
Remote programming by SMS
;IN1=0;IN2=4;ID1=10;ID2=0;DD1=0;DD2=15;
9.1.2
REMOTE REPORTING ALARM EVENTS
Parameters used to define the way to report the alarm event.
NOTE
SOLO-NX device send SMS messages for reporting alarm events.