CLMD16 Configuration Guide Rev.1.1 47
Step 2
:
Place the “Logic Outputs” of the “Fast and Slow” speed ECBs into “Toggle Elements”
Page 1: ...______________________________ CLMD16 16 Channel DC Load Controller Module Configuration Guide Revision 1 1 Copyright 2020 Carling Technologies Inc 60 Johnson Ave Plainville CT 06062 USA All Rights Re...
Page 2: ...Manual Mode 9 Configuring Hardwired Input Channels 10 Configuring Discrete I O Input Channels 12 Configurating Output Channels 13 Configurating Tank Level Inputs 14 Configuration of Common Circuit Typ...
Page 3: ...41 Single Input Load Control Sequence CLMD16 Does Something Different each Time the Same Button is Pressed 43 2 Speed Windshield Wiper Control 46 One Button Motor Speed Control PWM 50 For more Informa...
Page 4: ...This Page Intentionally Left Blank...
Page 5: ...3 software please visit https www maretron com products N2KAnalyzer php For N2KAnalyzer V3 software to configure a CLMD16 unit the CLMD16 unit must be powered and connected to an active NMEA2000 netwo...
Page 6: ...nter 2 Flash 3 Latch 4 Logic 5 Timer 6 Toggle 7 Toggle Mode Manual Mode Lastly connecting or mapping the output of these Switching Elements to the CLMD16 s ECB Electronic Circuit Breaker input signals...
Page 7: ...what Toggle and Momentary Inputs mean to the Switching Application It is important to understand that Inputs do not have to be a person pressing a switch but could be a signal becoming present This is...
Page 8: ...CLMD16 Configuration Guide___________________________________ 4 CLMD16 Configuration Guide Rev 1 1 Toggle Every time an Input becomes present or Turns On the Switching Application changes state...
Page 9: ...ough 48 The state of the output of Logic Element for the numbered channel Latch Output 1 through 16 The state of the output of Latch Element for the numbered channel Toggle Output 1 through 16 The sta...
Page 10: ...nd gap sizes Min and Max set points and user input signal delay parameters for CLMD16 output channels set to drive PWM Pulse Width Modulation See following Counter dialog for a description of the basi...
Page 11: ...k at configuration input required for this feature Logic Element If an ECB breaker requires combinatory Logic rules applied to it a Logic Element must be used Applying Logic Elements will help you to...
Page 12: ...r dialog for details on how to set up a Timer Element Toggle Element The Toggle element is a Latch element that does not require two separate Inputs to change state but instead can turn its Output bot...
Page 13: ...accessibility to only Network Inputs 1 16 from the Available Signals to be used as inputs within the Switching Application This feature can be used to funnel commands from any device using 127500 PGN...
Page 14: ...r example using the abovementioned High Level threshold of 8v if an input voltage of just about or just below 8v is detected where the input is fluctuating between under 8v and over 8v the input statu...
Page 15: ...____________________________________________________________ CLMD16 Configuration Guide Rev 1 1 11...
Page 16: ...ole and Indicator numbers corelating with the Discrete I O s every switch Apply the Discrete I O device s Data Instance and Indicator number to the CLMD16 s Discrete I O input channels to then enable...
Page 17: ...and ECB Type is configured By configuring the CLMD16 s ECB or Output Channels into the configuration first you then know where the final destination of the Inputs or abovementioned Switching Elements...
Page 18: ...l broadcast By clicking on Tank Levels Calibration another dialog box will appear See the following dialog depiction to understand how to enter the calibration data Please note the tank level calibrat...
Page 19: ...tact Input Signal to Switch a Load Applying a single momentary or sustained contact input signal to CLMD16 in order for the ECB output to replicate the input signal of On or Off is a one step procedur...
Page 20: ...ich the output of the Logic Element will be applied to the breaker s Input Signal In the following example there will be two input signals combined inside a Logic Element One input is from a hardwired...
Page 21: ...ever physical switch style the installer chooses therefore the input could be a sustained contact and no Toggle Element will be needed Multi Function Displays MFDs using 127500 Load Controller PGN or...
Page 22: ...C signal called Binary Event Low and one input is a momentary Discrete I O input called Discrete I O 1 both will be used to toggle the single CLMD16 load The following steps shows how to accurately co...
Page 23: ...an ECB is in Toggle Mode a Momentary Network Input signal becomes unaffected by the Toggle Mode In the following example there will be two momentary input sources and one Toggle Network Input signal...
Page 24: ...de Rev 1 1 Step 1 Assign inputs to a Logic Element Where 0 is Off and 1 is On configure the Logic Output in a manner to where if any input source is On the Logic Element s Output becomes active Step 2...
Page 25: ...Navigation Lights ECB is turned Off and Anchor Light ECB remains On In this example Discrete I O 1 is used for Navigation Lights and Discrete I O 2 is used for Anchor Light Step 1 Choose appropriate...
Page 26: ...signals into Toggle Elements Step 3 Create an intervening Logic Element for the Anchor Light circuit This Logic Element is used to ensure each time the Navigation Lights ECB Breaker 1 is On the Ancho...
Page 27: ..._______________________________ CLMD16 Configuration Guide Rev 1 1 23 Step 4 Place Toggle Output signal into Navigation Lights ECB and the intervening Logic Output signal into Anchor Light breaker inp...
Page 28: ...twork Inputs 1 2 to the scheme enabling the same Navigation Lights Logic behavior via Network Inputs 1 2 as long as the signal is a momentary type Input Signal The mapping for this exact circuit would...
Page 29: ...nput combination must be paid for proper operation Just as the previous circuit above Navigation Anchor Lights Toggle Logic using two Momentary Input Signals there will be rulesets that allow for Logi...
Page 30: ...____________________________ 26 CLMD16 Configuration Guide Rev 1 1 Step 2 Place Logic Output signals 1 and 3 into Toggle Elements Step 3 Place Toggle and Logic Output signals into ECB Input Signal loc...
Page 31: ...inserted before the Logic Elements 1 3 to enable the same Navigation Lights Logic behavior via Network Inputs 1 2 as long as the signal is a momentary type of Input Signal The mapping for this exact c...
Page 32: ...Find the original freshwater pump s control source in this example it is Network Input 5 Replicate the Input Signal of the original pump s Input Signal to the new secondary pump s Input Signal The se...
Page 33: ...oad called Mast Strobe The following steps will outline how to configure this load to automatically turn On Off with the frequency of On for 3 Sec and Off for 2 Sec triggered by a momentary input Step...
Page 34: ...Element shown here will only operate via Discrete I O 8 The same Flash behavior may be able to be replicated inside the internal logic of the equipment having direct control accessibility N2KView or...
Page 35: ...es not run dry potentially damaging the pump Using this circuit type can prevent unwanted damage to pumps as well as a way to keep fluid systems primed See the following example to setup this circuit...
Page 36: ...our Marker Point of 230 Ohms the next step will be to navigate to the Inputs Tab and create a Binary Event High Level based on this Marker Point The reason this is going to be a High Level indication...
Page 37: ...the freshwater pump load In this case it is Network Input 4 Remove Network Input 4 and add an available Logic Element In this example we are going to use Logic Output 4 Ensure Toggle Mode is Off as T...
Page 38: ...ell Select the logic element s output parameters such that when the Binary Event High signal is met the Logic Output turns off consequently turning off the freshwater pump Timed Delay Circuit Upon Inp...
Page 39: ...use a third party MFD using 127500 Load Controller PGN or any equipment running Maretron s N2KView software by default will have direct access to control ECB 4 Breaker 4 the Timer Element shown here w...
Page 40: ...Discrete I O 5 Momentary Input and called Gen Start Each Timer Element will trigger an ECB breaker output for each of the three actions the Generator will need to start Prime Preheat Start The generat...
Page 41: ...____________________________________ CLMD16 Configuration Guide Rev 1 1 37 Step 2 Apply Timer Outputs to appropriate Breaker Input Signals for each sequence function Prime Preheat Start Ensure Toggle...
Page 42: ...CLMD16 Configuration Guide___________________________________ 38 CLMD16 Configuration Guide Rev 1 1...
Page 43: ...ch Timer Element to enable the same Circuit Sequence behavior via Network Input 5 as long as the signal is a momentary type of Input Signal The mapping for this exact circuit would look as shown below...
Page 44: ...point is necessary for the circuit If only one control point is being used for this circuit place that control input in the stead of Logic Output 1 Step 2 Apply Logic Output to the Counter Element Sel...
Page 45: ...Scroll behavior to occur via Network Input such as control from Third Party MFD or N2KView Keep in mind One Button Smooth Scroll operates via momentary Input only If dimming a circuit from N2KView on...
Page 46: ...where if any input source is On the Logic Element s Output becomes active Step 2 Setup Counter where the Increment Signal is the Binary Event High signal and the Decrement Signal is Binary Event Low B...
Page 47: ...e set in accordance with the defining voltages that the CLMD16 will be receiving from your input source Single Input Load Control Sequence CLMD16 Does Something Different each Time the Same Button is...
Page 48: ...Step 2 Place the circuit control input into a Latch Element Set Signal The output of the first Toggle Element goes into the Reset Signal Creating another Latch Element place the output of the first To...
Page 49: ...O 1 The same Toggle Sequence behavior may be able to be replicated inside the internal logic of the equipment having direct control accessibility N2KView or if this logic needs to be accessed by thir...
Page 50: ...when the High or Low operations are On and restore to the On state when Fast and Slow are Off The control for this circuit will be Discrete I O 5 for Fast and Discrete I O 6 for Slow See the following...
Page 51: ...____________________________________________________________ CLMD16 Configuration Guide Rev 1 1 47 Step 2 Place the Logic Outputs of the Fast and Slow speed ECBs into Toggle Elements...
Page 52: ...gle Elements and the single Logic Element into the ECBs Input Signals ensure Toggle Mode is Off Because damage to the motor can occur if operated incorrectly it is best this circuit has Manual Mode en...
Page 53: ...equipment having direct control accessibility N2KView or any third party MFD using 1275000 Load Controller PGN If this logical circuit needs to be accessed by third party MFD two combinatory Logic Ele...
Page 54: ...d to enable the Park signal for the wiper motor The Park signal needs to be On whenever the wiper motor power speed control ECB is Off The following example shows how this circuit type will be arrange...
Page 55: ...ode is On for this ECB Set the ECB parameters for the windshield wiper Park signal choosing an available Logic Element as the Input Signal Ensure Toggle Mode is Off for this ECB Because the ECB used f...
Page 56: ...ogic of any equipment having direct control accessibility to the ECBs including N2KView or any third party MFD using 1275000 Load Controller PGN If this logical circuit needs to be accessed by third p...
Page 57: ...____________________________________________ CLMD16 Configuration Guide Rev 1 1 53 For more Information For further information about Maretron s MPower Digital Switching solutions please visit https w...
Page 58: ......