VALVE REMAINS OPEN IN THE FREEZE CYCLE:
Symptoms of a hot gas valve remaining partially open
during the freeze cycle can be similar to symptoms of an
expansion valve, capillary tube or compressor problem.
Symptoms are dependent on the amount of leakage in the
freeze cycle.
A small amount of leakage will cause increased freeze
times and the ice formation pattern on the top of the
evaporator will be too thin, but a complete ice cube will
eventually form.
Refer to the Parts Manual for proper valve application.
If replacement is necessary, use only “original” Welbilt
replacement solenoid valves.
Use the following procedure to help determine if a harvest
valve is remaining partially open during the freeze cycle:
1. Wait 5 minutes into the freeze cycle.
2. Feel the inlet of the hot gas valve.
Important
Feeling the hot gas valve outlet or across the hot gas
valve itself will not work for this comparison. The hot
gas valve outlet is on the suction side (cool refrigerant).
It may be cool enough to touch even if the valve is
leaking.
3. Feel the compressor discharge line.
Summary of Contents for UG Series
Page 1: ...Part Number 040006847 12 19 UnderCounter Ice Machines UG Series Technician s Handbook ...
Page 2: ......
Page 12: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 19: ...Part Number 040006847 12 19 19 Model Serial Number Location Model Serial Number Location ...
Page 30: ...PAGE INTENTIONALLY LEFT BLANK 30 Part Number 040006847 12 19 ...
Page 80: ...PAGE INTENTIONALLY LEFT BLANK 80 Part Number 040006847 12 19 ...
Page 92: ...PAGE INTENTIONALLY LEFT BLANK 92 Part Number 040006847 12 19 ...
Page 108: ...108 Part Number 040006847 12 19 PAGE INTENTIONALLY LEFT BLANK ...
Page 125: ......
Page 126: ......
Page 127: ......