68
Part Number: 040006847 12/19
BIN THERMISTOR (T3)
Function
The bin thermistor stops the ice machine when the
bin is full. When ice cubes contact the bin thermistor
bulb holder, the bin thermistor opens and stops the
ice machine. When ice cubes no longer contact the bin
thermistor bulb holder, the bin thermistor closes and the
ice machine starts.
The bin thermistor “temperature setting” is determined by
the point of T2 (liquid line thermistor) at the time when T1
(sump water thermistor) comes below 2 °C. Refer to the
Specifications Charts below for clearance.
Specifications
UG18/UG20/UG30
T1 ( ̊C)
T2 ( ̊C)
Shut down
(T3)
Power on
(T3)
≤2.0
T2≤32
≤1.7
≥2.2
≤2.0
32 <T2≤51
≤2.2
≥3.7
≤2.0
51 <T2
≤3.0
≥4.5
UG40/UG50/UG65
T1 ( ̊C)
T2 ( ̊C)
Shut down
(T3)
Power on
(T3)
≤2.0
T2≤28
≤1.5
≥2.0
≤2.0
28 <T2≤56
≤2.0
≥3.5
≤2.0
56 <T2
≤3.0
≥4.5
UG80
T1 ( ̊C)
T2 ( ̊C)
Shut down
(T3)
Power on
(T3)
≤2.0
T2≤37
≤1.5
≥2.0
≤2.0
37 <T2≤56
≤2.0
≥3.5
≤2.0
56 <T2
≤3.0
≥4.5
Summary of Contents for UG Series
Page 1: ...Part Number 040006847 12 19 UnderCounter Ice Machines UG Series Technician s Handbook ...
Page 2: ......
Page 12: ...PAGE INTENTIONALLY LEFT BLANK ...
Page 19: ...Part Number 040006847 12 19 19 Model Serial Number Location Model Serial Number Location ...
Page 30: ...PAGE INTENTIONALLY LEFT BLANK 30 Part Number 040006847 12 19 ...
Page 80: ...PAGE INTENTIONALLY LEFT BLANK 80 Part Number 040006847 12 19 ...
Page 92: ...PAGE INTENTIONALLY LEFT BLANK 92 Part Number 040006847 12 19 ...
Page 108: ...108 Part Number 040006847 12 19 PAGE INTENTIONALLY LEFT BLANK ...
Page 125: ......
Page 126: ......
Page 127: ......