PRESSURE TEST AND EVACUATE THE LINE SET
AND CVD CONDENSING UNIT
Schrader valve core removal tools that allow for
removal and installation of the valve cores without
removing manifold gauge set hoses are recommended
to decrease the evacuation time.
Leave the line set shut-off valves closed (front seated).
All CVD condensing units manufactured after
December 2009
contain a check valve in the
compressor discharge line.
The check valve
requires an additional connection on the condensing
unit during evacuation and recovery procedures.
Connections are required at five points:
Ice Machine Head Section
1. Receiver Service Valve
2. Low Side Access Valve
3. High Side Access Valve
CVD Condensing Unit
4. Compressor Discharge Access Valve
5. Suction Filter Access Valve
Summary of Contents for SD0672C
Page 2: ......
Page 65: ...Part Number 80 1505 3 6 11 65 This Page Intentionally Left Blank ...
Page 66: ...66 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Page 79: ...Part Number 80 1505 3 6 11 79 A B C D ...
Page 81: ...Part Number 80 1505 3 6 11 81 A B C D E I ...
Page 90: ...90 Part Number 80 1505 3 6 11 A B C D E F G ...
Page 94: ...94 Part Number 80 1505 3 6 11 A B C E F D G H ...
Page 97: ...Part Number 80 1505 3 6 11 97 A B C D F G E ...
Page 100: ...100 Part Number 80 1505 3 6 11 A B C D E F G H ...
Page 174: ...174 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Page 198: ...198 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Page 229: ...Part Number 80 1505 3 6 11 229 SV1406 USING PINCH OFF TOOL ...
Page 232: ...232 Part Number 80 1505 3 6 11 ...
Page 238: ...238 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Page 276: ...276 Part Number 80 1505 3 6 11 S3070C 230V 50HZ 1PH ...
Page 283: ...Part Number 80 1505 3 6 11 283 CVD3085 380V 50HZ 3PH ...
Page 296: ...296 Part Number 80 1505 3 6 11 This Page Intentionally Left Blank ...
Page 297: ......