Safety Limit #1
Refer to page 134 for description.
Possible Cause Checklist
Improper Installation
Refer to “Installation/Visual Inspection Checklist”
Water System
Low water pressure (20 psig min.)
High water pressure (80 psig max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective water fill valve
Dirty/defective float valve
Dirty/defective water dump valve
Defective water pump
Loss of water from sump area
Electrical System
Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Contactor not energizing
Compressor electrically non-operational
High inlet air temperature (130°F/54.4°C max.)
Condenser discharge air recirculation
Defective fan cycling control
Defective fan motor
Restricted condenser air flow
Refrigeration System
Non-Manitowoc components
Improper refrigerant charge
Defective head pressure control
Defective cool vapor valve
Defective compressor
TXV starving or flooding (check bulb mounting)
Non-condensable in refrigeration system
Plugged or restricted high side refrigerant lines or
component
Restricted air flow/dirty condenser fins