4
TPM 087/12
Tab. 2.1.1. Actuating mechanism BELIMO BLE 24(-ST), BLE 230
Actuating mechanism
BELIMO
BLE 24(-ST)
BLE230
Nominal voltage
AC 24V 50/60Hz
DC 24 V
AC 230 V 50/60Hz
Power consumption - motoring
- holding
7,5 W
< 0,5 W
5W
< 1 W
Dimensioning
9 VA (Imax 2,7 A @ 5 ms)
12 VA (Imax 6 A @ 5 ms)
Protection class
III
II
Degree of protection
IP 54
Running time for 95°
< 30 s
Ambient temperature range
Non-operating temperature
- 30 °C … + 50 °C
- 40 °C … + 80 °C
Connecting - motor
- auxiliary switch
cable 1 m, 3 x 0,75 mm
cable 1 m, 6 x 0,75 mm
(BLE 24-ST) with plug-in connectors
Fig. 3
Actuating mechanism BELIMO BLE 24(-ST)
Fig. 4
Actuating mechanism BELIMO BLE 230
AC 24 V
~
+
-
DC 24 V
S2
S1
S3
S5
S4
S6
BLE24 (-ST)
BLE24-ST: Design with connector plugs for communication
Connection through
an insulation transformer.
to network and communication device BKNE230-24
Parrallel connection of other driver is possible.
Pay attention to the power input data.
2
1
3
<3°
<87°
BLE230
AC230 V
2
1
N
S3
S2
S1
S6
S5
S4
<3°
<87°
Parrallel connection of other driver is possible.
Pay attention to the power input data.
3
L1
2
2
Summary of Contents for SEDM