TPM 087/12
1. Description
1.1.
Smoke extraction dampers - multi are shutters in the smoke exhaust piping systems. The
dampers are designed to remove heat and combustible products (e.g. smoke) from effected fire
compartments. In the event of fire the Smoke and Fire ventilation system opens the damper in
the affected section and removes combustion products and heat from this section.
The damper blade is controlled by electrical actuating mechanism.
Dampers are fire resistant and are intended for systems with manual or automatic activation.
Dampers are designed for using in fire compartments that can be connected to the smoke
exhaust ducts (tested according to EN 1366-8) or they can be installed in or on the construction
of the fire compartment.
Dampers can be delivered with or without flanges.
II. GENERAL INFORMATION
Supporting Construction
Classification
Horizontal duct system
EI 120 (h
od
- i
↔
o) S1000C
10000
HOT 400/30MAmulti
EI 120 (h
od
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
Porous concrete ceiling construction,
thickness 150 mm
EI 120 (h
ow
- i
↔
o) S1500C
10000
HOT 400/30AAmulti
Porous concrete wall construction,
thickness 100 mm
EI 120 (v
ew
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
EI 90 (v
ew
- i
↔
o) S1500C
10000
HOT 400/30AAmulti
Gypsum wall, thickness 100 mm
EI 120 (v
ew
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
EI 90 (v
ew
- i
↔
o) S1500C
10000
HOT 400/30AAmulti
Vertical duct system
EI 120 (v
ed
- i
↔
o) S1000C
10000
HOT 400/30MAmulti
EI 120 (v
ed
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
Tab. 1.2.1. Classification of Dampers
Fig. 1 Damper SEDM
1.2.
Damper characteristics
• CE certified acc. to EN 12101-8
• Tested in accordance with EN 1366-10
• Classified acc. to EN 13501-4+A1
• Fire resistance according Tab. 1.2.1
• External Casing leakage class C, Internal leakage min. class 2 acc. to EN 1751
• Cycling test in class C 10000 acc. to EN 15650
• ES Certificate of conformity No. 1391-CPD-0098/2012
• Declaration of Perfomance No. CDM/SEDM/001/13
• Hygienic assessment of fire dampers - Report No. 1.6/13/16/2