42
TPM 087/12
VIII. PRODUCT DATA
16. Nameplate
16.1.
Nameplate is placed on the damper casing
Fig. 32 Nameplate
Certificate:
WEIGHT (kg):
SMOKE EXTRACTION DAMPER - MULTI SEDM
DESIGN:
SERIAL NUMBER:
DIMENSION:
1391
1391-CPD-0098/2012/O
12
EN 12101-8:2011
CLASSIFICATION:
acc.certificate 1391-CPD-0098/2012/O
TPM087/12
MANDÍK, a.s., Dob
ř
íšská 550, 267 24 Hostomice, Czech Republic
17. Quick review
Smoke exhaust damper
SEDM
Size
A = 180 - 1600 mm
B = 180 - 1000 mm
Placement
wall/
celing
Filling of space
between damper
and wall
Fire resistance
Fig.
min.
thickness
[mm]
In solid wall con-
struction
100
mineral stone
wool, surface is
covered by fire
protection mastic
and cement lime
plate
EI 120 (v
ew
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
17, 18
In solid ceiling
construction
150
mineral stone
wool, surface is
covered by fire
protection mastic
and cement lime
plate
EI 90 (h
ow
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
19, 20
In gypsum wall
construction
100
mineral stone
wool, surface is
covered by fire
protection mastic
and cement lime
plate
EI 120 (v
ew
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
21
On solid wall
construction
100
-
EI 120 (v
ew
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
22, 23
On solid ceiling
construction
150
-
EI 90 (h
ow
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
24, 25
Vertical duct in-
stallation
-
-
EI 120(h
od
- i
↔
o) S1000C
10000
HOT 400/30MAmulti
EI 120 (h
od
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
26
Horizontal duct
installation
-
-
EI 120 (v
ed
- i
↔
o) S1000C
10000
HOT 400/30MAmulti
EI 120 (v
ed
- i
↔
o) S1000C
10000
HOT 400/30AAmulti
27
Tab. 17.1.1.
Quick review
Summary of Contents for SEDM