background image

Smoke extraction damper - SEDM-D

Page 20

Version 2023-06-07

TPM 155/22

1)

Drill a hole in the corner of the damper for a connecting cable, prepare a cable passage in the shaft wall.

2)

Check that all cage nuts or other elements necessary for the connection of the grille are on the damper.

3)

Fill the inside of the damper frame with mastic, mortar or gypsum.

4)

Install SEDM-D into the centre of installation opening using wedges or spacers.

5)

Pull the connecting cable including a special grommet through the wall.

6)

Fill the gap between the damper and a shaft with mastic, mortar or gypsum. Make sure that the gap is
perfectly filled. Let the mastic (mortar or gypsum) harden.

7)

Drill four holes to the damper casing in the place of corners (4 x horizontal) up to the shaft wall, screw the
damper into the shaft wall.

8)

Connect the cable to the junction box, secure the cable on the inside of the damper casing against pulling
the end out of the junction box using cable clips.

9)

Seal the cable passage through the shaft wall and through the damper casing.

10)

 Attach a shock absorber to the shaft wall or damper blade.

11)

Test opening and closing of the damper blade.

12)

 Install a grille.

Installation without installation frame

1)

Install frame into the opening. For frame installation procedure 

→ see page 23

2)

Drill a hole in the corner of the damper for a connecting cable, prepare a cable passage in the shaft wall.

3)

Check that all cage nuts or other elements necessary for the connection of the grille are on the damper.

4)

Install SEDM-D on the frame and mount it on four fastening plates.

5)

Pull the connecting cable including the special grommet through the shaft wall.

6)

Connect the cable to the junction box, secure the cable on the inside of the damper casing against pulling
the end out of the junction box using cable clips.

7)

Seal the cable passage through the shaft wall and through the damper casing.

8)

Attach a shock absorber to the shaft wall or damper blade.

9)

Test opening and closing of the damper blade.

10)

 Install a grille.

Installation with installation frame

Dampers can be installed with the restraint mechanism left or right.

Installation procedure

Summary of Contents for SEDM-D

Page 1: ...267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz SEDM D Smoke extraction damper multi Technical Documentation Installation Commissioning Operation Maintenance and Service M...

Page 2: ...IMENSIONS 15 Technical parameters 16 V INSTALLATION 18 Placement and Installation 18 Statement of installations 19 Installation procedure 20 Cable connection 21 Shock absorber 22 Installation frame 22...

Page 3: ...or The dampers consist of a single calcium silicate blade reinforced by steel crossbeams hanged on spring equipped hinges combined calcium silicate and aluminum frame a cold seal silicon gasket and a...

Page 4: ...underpressure 1500 Pa overpressure 500 Pa Closed blade tightness class 3 according to EN 1751 Certificate of Constancy of Performance No 1391 CPR 2023 0030 Declaration of Performance No PM SEDM D 01...

Page 5: ...perature and with a temperature range of 25 C to 50 C Connecting cables shall be guided from a pre punched hole in one of the corners of the damper frame to the junction box using delivered cable clip...

Page 6: ...in accordance with NF 61 937 10 Hand operated rearming design with a magnet voltage of 48 V DC and with two end switches signaling of the damper blade position CLOSED STAND BY and OPEN SECURITY Electr...

Page 7: ...esistance Insulation voltage open contact Cut off power DC Longevity cycles 0 5 A 0 1 Ohm 500 V 10 W 1000 Microswitch AC rating Microswitch degree of protection 230 V AC 5 A IP67 Compliance NF 61 937...

Page 8: ...arming time at room temperature Longevity cycles Cycling period 40 s 30 s 300 min 120 s Maintenance maintenance free Compliance NF 61 937 1 NF 61 937 10 Rearming of the damper blade with electric moto...

Page 9: ...amper should be used with a protection grille G1 G2 G3 or G4 Grille G1 is not powder painted as standard Can be powder painted if specified in the ordering key Grilles G2 G3 G4 are powder painted If n...

Page 10: ...mm 12 mm 14 mm from the wall Detail A Section view 2 2 5 m m 4x Screw M5 for hanging the grille Grille G3 Design grille with thin louvers made from Al sheet no visible bolts easy to open and close 95...

Page 11: ...test Continuous operation test at 20 C 70 C for 1 hour 5 hours Compliance NF 61 937 1 NF 61 937 10 End switches Type configuration G905 C NO NC Voltage 60 V DC Switchable DC current Contact resistanc...

Page 12: ...O1 C End switch position open input 9 yellow FC O2 NO End switch position open normally open 10 green FC O3 NC End switch position open normally contact 11 blue FCB F1 C End switch position closed in...

Page 13: ...ON the voltage of 24 V DC or 48 V DC respectively on MAG and MAG for at least 1 second to activate the damper To test the damper during the commissioning with the protection grille removed or open the...

Page 14: ...e 7 Installing or closing and securing the protection grille For larger dampers it may be necessary to use both hands to rearm the damper and proceed in 7 steps Rearming electric motor design 1 Switch...

Page 15: ...ing motor optional 6 Restraint mechanism 7 End switch module optional 8 Damper blade B H B H B 73 H 68 90 Dimensions without grille 80 built in depth Dimensions for mounting of grilles B 39 H 180 1 2...

Page 16: ...85 0 1615 8 4 0 9 1 5 2 1 1 8 1 6 550 0 1610 8 4 0 9 1 6 2 3 1 9 1 6 400 0 1685 8 5 0 9 1 5 2 1 1 9 1 6 600 0 1767 9 0 9 1 7 2 5 2 1 7 450 0 1916 9 2 0 9 1 6 2 3 2 1 7 650 0 1924 9 5 1 1 9 2 6 2 1 1 7...

Page 17: ...2 7 2 2 350 0 2079 9 4 1 1 7 2 3 2 2 1 8 650 0 3457 13 1 4 2 7 3 2 2 9 2 2 385 0 2311 10 4 1 1 1 9 2 5 2 3 1 9 700 0 3739 13 7 1 4 2 9 3 4 3 2 3 400 0 2411 10 7 1 1 2 2 5 2 4 1 9 750 0 4021 14 4 1 5...

Page 18: ...r is built in the damper blade should not grind against the damper casing during opening or closing The distance between the damper and the construction must be 75 mm at the minimum according to EN 13...

Page 19: ...nce class for the given pressure e g 40 mm PROMATECT L 500 45 mm THERMAX SL Tecniver 45 mm GEOTEC S 35 mm GEOFLAM F 35 mm GEOFLAM F Light Mortar or gypsum EI 90 ved i o S1500C300AAmulti 27 Mastic 27 I...

Page 20: ...cable passage through the shaft wall and through the damper casing 10 Attach a shock absorber to the shaft wall or damper blade 11 Test opening and closing of the damper blade 12 Install a grille Inst...

Page 21: ...special grommet through the shaft wall and the damper Connect the cable to the junction box and secure it to the cable clips with cable ties Secure the cable against pulling the end out of the juncti...

Page 22: ...cements 5 Rubber seal 6 Promaseal Installation frame is delivered separately Shaft from concrete or aerated concrete Shaft from fire resistant panels Use a shock absorber that is delivered with the da...

Page 23: ...to the opening and fix it with screws Screws 4x30 from the front side of the frame and screws 5x50 from the inner side Fill the gap between the frame and shaft with mastic mortar or gypsum Make sure t...

Page 24: ...oke extraction damper SEDM D Page 24 Version 2023 06 07 TPM 155 22 5 Prepare SEDM D and set four fastening plates to the open position 6 Install SEDM D on the frame and mount it on four fastening plat...

Page 25: ...oncrete With mastic mortar or gypsum B 10 H 10 70 Installation opening 1 Concrete or aerated concrete 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 S...

Page 26: ...tion opening 1 Concrete or aerated concrete 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Installation frame installation procedure see page 23 5 Ins...

Page 27: ...A 1 Fire resistant panels 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Screw 5x70 mm 4x connection of the damper with shaft X shaft wall thickness...

Page 28: ...Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Installation frame installation procedure see page 23 5 Installation frame and damper fastening plate 4x X X 80 80 Detail A A B 20 5 Inst...

Page 29: ...913 0 828 500 2 290 1 870 1 569 1 344 1 170 1 032 0 921 0 829 0 752 550 2 075 1 695 1 422 1 218 1 060 0 935 0 834 0 751 0 681 600 1 879 1 534 1 287 1 102 0 960 0 847 0 755 0 680 0 617 650 1 700 1 388...

Page 30: ...dust free environment out of direct sunlight Ensure protection against moisture and extreme temperatures minumum temperature 5 C The dampers must be protected against mechanical and accidental damage...

Page 31: ...to operation after assembly and after sequential revisions checks and functionality tests of all designs including operation of the electrical components must be successfully provided and finished Che...

Page 32: ...g design with a magnet voltage of 24 V DC and with two end switches 24C2M Electric motor rearming design with a magnet voltage of 24 V DC and with two pairs of end switches 24C4M Electric motor rearmi...

Page 33: ...th thin louvers with hidden bolts G4 design grille from drawn steel Grille colour RAL F SEDM D 500x500 Size B width x H height Accessories Grille Installation frame RESTRAINT MECHANISM SEDM D 24 V Spa...

Page 34: ...m The producer reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mand...

Reviews: