Smoke extraction damper - SEDM-D

TPM 155/22

SEDM-D rearming motor design

SEDM-D hand-operated design

Operating conditions

Both declared performance and faultless operation are ensured under the following conditions:

The damper equipped with one of the grilles available

Maximum vacuum up to 1500 Pa or overpressure up to 500 Pa

Rearming shall be carried out without air flow and without air pressure

The dampers are suitable for vertical installation only

Range of activation voltage and rearming motor supply voltage shall be respected; dimensioning of voltage sources and of
connecting cables shall fit the electrical parameters of the damper

Connecting cables shall not physically impede free movement of moving parts and sub-asemblies

Damper shall be always kept closed with the exception of short periods of installation, commissioning and functional tests

The rearming motor shall not be used to act against the air pressure or another external force

Dampers  are  designed  for  macroclimatic  areas  with  mild  climate  according  to  EN  IEC  60  721-3-3  ed.2.,  class  3K22.
(Environment 3K22 is typically protected place with regulated temperature) and with a temperatu

re range of -25°C to 50°C

Connecting cables shall be guided from a pre-punched hole in
one of the corners of the damper frame to the junction box
using  delivered  cable  clips.  The  junction  box  contains  a
universal 10-position screw terminal. Damper supply voltage
and terminal block positions are printed inside the junction
box.  Depending  on  the  damper  design  configuration  and
connecting  cables  available,  some  terminal  positions  may
stay  void.  Aditional  junction  box  with  6-position  screw
terminal is present for bipolar end-switch module.

The damper is equipped with a restraint mechanism  keeping
the  damper  closed.  The  restraint  mechanism  includes  a
permanent  magnet  combined  with  an  electric  coil  with

magnetic poles opposite to those of the permanent magnet.
In case of the activation of the damper, the coil magnetic field
compensates the magnetic field of the magnet and thus, the
restraint  mechanism  lets  the  damper  open.  The  activation
signal  represents  a  simple  switching  the  voltage  ON.  The
damper  may  be  equipped  with  position  end-switch  module
with end-switches indicating the damper blade position open
or  closed.  The  damper  is  manufactured  in  hand-operated
rearming design or electric motor rearming design. Rearming
means  getting  the  damper  blade  from  the  position  open
(security) to the position closed (stand-by).

II. DESIGN

Summary of Contents for SEDM-D

Page 1: ...267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz SEDM D Smoke extraction damper multi Technical Documentation Installation Commissioning Operation Maintenance and Service M...

Page 2: ...IMENSIONS 15 Technical parameters 16 V INSTALLATION 18 Placement and Installation 18 Statement of installations 19 Installation procedure 20 Cable connection 21 Shock absorber 22 Installation frame 22...

Page 3: ...or The dampers consist of a single calcium silicate blade reinforced by steel crossbeams hanged on spring equipped hinges combined calcium silicate and aluminum frame a cold seal silicon gasket and a...

Page 4: ...underpressure 1500 Pa overpressure 500 Pa Closed blade tightness class 3 according to EN 1751 Certificate of Constancy of Performance No 1391 CPR 2023 0030 Declaration of Performance No PM SEDM D 01...

Page 5: ...perature and with a temperature range of 25 C to 50 C Connecting cables shall be guided from a pre punched hole in one of the corners of the damper frame to the junction box using delivered cable clip...

Page 6: ...in accordance with NF 61 937 10 Hand operated rearming design with a magnet voltage of 48 V DC and with two end switches signaling of the damper blade position CLOSED STAND BY and OPEN SECURITY Electr...

Page 7: ...esistance Insulation voltage open contact Cut off power DC Longevity cycles 0 5 A 0 1 Ohm 500 V 10 W 1000 Microswitch AC rating Microswitch degree of protection 230 V AC 5 A IP67 Compliance NF 61 937...

Page 8: ...arming time at room temperature Longevity cycles Cycling period 40 s 30 s 300 min 120 s Maintenance maintenance free Compliance NF 61 937 1 NF 61 937 10 Rearming of the damper blade with electric moto...

Page 9: ...amper should be used with a protection grille G1 G2 G3 or G4 Grille G1 is not powder painted as standard Can be powder painted if specified in the ordering key Grilles G2 G3 G4 are powder painted If n...

Page 10: ...mm 12 mm 14 mm from the wall Detail A Section view 2 2 5 m m 4x Screw M5 for hanging the grille Grille G3 Design grille with thin louvers made from Al sheet no visible bolts easy to open and close 95...

Page 11: ...test Continuous operation test at 20 C 70 C for 1 hour 5 hours Compliance NF 61 937 1 NF 61 937 10 End switches Type configuration G905 C NO NC Voltage 60 V DC Switchable DC current Contact resistanc...

Page 12: ...O1 C End switch position open input 9 yellow FC O2 NO End switch position open normally open 10 green FC O3 NC End switch position open normally contact 11 blue FCB F1 C End switch position closed in...

Page 13: ...ON the voltage of 24 V DC or 48 V DC respectively on MAG and MAG for at least 1 second to activate the damper To test the damper during the commissioning with the protection grille removed or open the...

Page 14: ...e 7 Installing or closing and securing the protection grille For larger dampers it may be necessary to use both hands to rearm the damper and proceed in 7 steps Rearming electric motor design 1 Switch...

Page 15: ...ing motor optional 6 Restraint mechanism 7 End switch module optional 8 Damper blade B H B H B 73 H 68 90 Dimensions without grille 80 built in depth Dimensions for mounting of grilles B 39 H 180 1 2...

Page 16: ...85 0 1615 8 4 0 9 1 5 2 1 1 8 1 6 550 0 1610 8 4 0 9 1 6 2 3 1 9 1 6 400 0 1685 8 5 0 9 1 5 2 1 1 9 1 6 600 0 1767 9 0 9 1 7 2 5 2 1 7 450 0 1916 9 2 0 9 1 6 2 3 2 1 7 650 0 1924 9 5 1 1 9 2 6 2 1 1 7...

Page 17: ...2 7 2 2 350 0 2079 9 4 1 1 7 2 3 2 2 1 8 650 0 3457 13 1 4 2 7 3 2 2 9 2 2 385 0 2311 10 4 1 1 1 9 2 5 2 3 1 9 700 0 3739 13 7 1 4 2 9 3 4 3 2 3 400 0 2411 10 7 1 1 2 2 5 2 4 1 9 750 0 4021 14 4 1 5...

Page 18: ...r is built in the damper blade should not grind against the damper casing during opening or closing The distance between the damper and the construction must be 75 mm at the minimum according to EN 13...

Page 19: ...nce class for the given pressure e g 40 mm PROMATECT L 500 45 mm THERMAX SL Tecniver 45 mm GEOTEC S 35 mm GEOFLAM F 35 mm GEOFLAM F Light Mortar or gypsum EI 90 ved i o S1500C300AAmulti 27 Mastic 27 I...

Page 20: ...cable passage through the shaft wall and through the damper casing 10 Attach a shock absorber to the shaft wall or damper blade 11 Test opening and closing of the damper blade 12 Install a grille Inst...

Page 21: ...special grommet through the shaft wall and the damper Connect the cable to the junction box and secure it to the cable clips with cable ties Secure the cable against pulling the end out of the juncti...

Page 22: ...cements 5 Rubber seal 6 Promaseal Installation frame is delivered separately Shaft from concrete or aerated concrete Shaft from fire resistant panels Use a shock absorber that is delivered with the da...

Page 23: ...to the opening and fix it with screws Screws 4x30 from the front side of the frame and screws 5x50 from the inner side Fill the gap between the frame and shaft with mastic mortar or gypsum Make sure t...

Page 24: ...oke extraction damper SEDM D Page 24 Version 2023 06 07 TPM 155 22 5 Prepare SEDM D and set four fastening plates to the open position 6 Install SEDM D on the frame and mount it on four fastening plat...

Page 25: ...oncrete With mastic mortar or gypsum B 10 H 10 70 Installation opening 1 Concrete or aerated concrete 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 S...

Page 26: ...tion opening 1 Concrete or aerated concrete 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Installation frame installation procedure see page 23 5 Ins...

Page 27: ...A 1 Fire resistant panels 2 Fire resistant mastic E g HILTI Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Screw 5x70 mm 4x connection of the damper with shaft X shaft wall thickness...

Page 28: ...Firestop Acrylic coating SFS S ACR mortar or gypsum 3 SEDM D 4 Installation frame installation procedure see page 23 5 Installation frame and damper fastening plate 4x X X 80 80 Detail A A B 20 5 Inst...

Page 29: ...913 0 828 500 2 290 1 870 1 569 1 344 1 170 1 032 0 921 0 829 0 752 550 2 075 1 695 1 422 1 218 1 060 0 935 0 834 0 751 0 681 600 1 879 1 534 1 287 1 102 0 960 0 847 0 755 0 680 0 617 650 1 700 1 388...

Page 30: ...dust free environment out of direct sunlight Ensure protection against moisture and extreme temperatures minumum temperature 5 C The dampers must be protected against mechanical and accidental damage...

Page 31: ...to operation after assembly and after sequential revisions checks and functionality tests of all designs including operation of the electrical components must be successfully provided and finished Che...

Page 32: ...g design with a magnet voltage of 24 V DC and with two end switches 24C2M Electric motor rearming design with a magnet voltage of 24 V DC and with two pairs of end switches 24C4M Electric motor rearmi...

Page 33: ...th thin louvers with hidden bolts G4 design grille from drawn steel Grille colour RAL F SEDM D 500x500 Size B width x H height Accessories Grille Installation frame RESTRAINT MECHANISM SEDM D 24 V Spa...

Page 34: ...m The producer reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mand...

Reviews: