MANDÍK CPV Installation, commissioning, and maintenance
IZU 02/2021
MANDÍK, a.s., www.mandik.cz
R
34
9.5
GENERAL OPERATION AND MAINTENANCE OF THE UNIT
Anyone conducting maintenance on air handling units must be familiar with the maintenance
instructions and adhere to the recommendations specified therein. These instructions are an
additional source of information and anticipate knowledge of the rules of assembly and
operation for CPV class air handling units
from MANDÍK, a.s. and adherence to all the
requirements specified therein. The manufacturer assumes no liability for any damage
caused by the failure to adhere to such rules of assembly and operation and these
instructions.
Air handling units are used to condition and convey air and require regular cleaning and
maintenance. Based on the scope and intended use of HVAC equipment, and the components,
composition and the features of the air handler itself, we recommend operators draft local
operating and maintenance regulations that fully comply with the requirements of the rules of
assembly and operation and instructions for the maintenance of CPV class air handling units
from MANDÍK, a.s.
1
3
6
12
8.
PLATE RECUPERATOR
8.01.
N
repair / replace
8.02.
N
clean
8.03.
N
repair / replace
8.04.
N
clean
8.05.
N
repair / clean
8.06.
N
clean / repair
8.07.
N
repair
* unit in operation when performing this inspection
Intervals (months)
Unit in
operatio
n Y / N *
Inspection action
Inspection for damage to heat exchange
surfaces on the heat exchanger.
Inspection of the status and pouring water in
the condensate drain trap
Inspection for cleanliness of heat exchange
surfaces on the heat exchanger.
Inspection for free rotation of the by-pass /
mixing dampers.
Method of service
/ removal
Inspection of the condition and cleanliness of
the condensate drip eliminator
Inspection of the cleanliness and continuity of
the condensate drain.
Inspection for damper fouling.
1
3
6
12
9.
TERMINAL DAMPERS
9.01.
N
repair / replace
9.02.
N
clean
* unit in operation when performing this inspection
Inspection for damper fouling.
Method of service
/ removal
Intervals (months)
MAINTENANCE AND SERVICE ACTIVITIES
Unit in
operation
Y / N *
Inspection action
Inspection for free rotation of dampers.