www.mc-techgroup.com
LA | 1.01.01
23
14.4
ADJUSTMENT OF ALARM HOLDING FUNCTION
A self-retaining of the alarm is optionally configurable. In the event of an alarm, a manual reset must
then be carried out.
The following steps must be carried out to set up the alarm hold function:
•
For the
LA1.1
electronic controller, remove the 4 cover screws and then the cover.
•
For the rail mounting version
LA1.4,
loosen the locking mechanism at the top and bottom behind
the terminals using a screwdriver. Then pull the printed circuit board together with the housing
front out of the rear housing part.
•
Jumper at JP1 from position 2-3 (no alarm memory function) to position 1-2 (see Figure 4 or
Figure 6).
•
For the
LA1.1
electronic controller, screw on the cover again.
•
For the
LA1.4
electronic controller, push the printed circuit board back into the housing.
To reset the electronic controller
LA1.1
manually, remove the 4 cover screws, remove the cover and
then press button
“S1” (see Figure 4).
To reset the electronic controller
LA1.4
manually,
press the button “Al. Reset” at the housing front.
15
CLOSING DOWN
No special measures need to be taken for decommissioning.
16
MAINTENANCE AND REPAIR
N O T E !
Before any maintenance and repair work, the installation-specific
and process-specific safety measures must be observed!
The LA
®
series liquid control units operate maintenance-free over a long period of time.
It is possible that the electrodes of the
LA1S
or
LA 25S
sensors are soiled with deposits. Use a cloth
for cleaning, if necessary with solvent or cleaning agent. The sensor needs to be disassembled for
cleaning.
A T T E N T I O N !
In the event of a liquid ingress, the entire conditioning system,
including the mounting assembly with sensor, must be dried and
cleaned.
Summary of Contents for LA Series
Page 26: ...26 LA 1 01 01 www mc techgroup com Figure 8 Flow diagram LA1 1 115 230 V 50 60 Hz ...
Page 27: ...www mc techgroup com LA 1 01 01 27 Figure 9 Flow diagram LA1 1 24V AC DC ...
Page 28: ...28 LA 1 01 01 www mc techgroup com Figure 10 Flow diagram LA1 4 115 230V 50 60Hz ...
Page 29: ...www mc techgroup com LA 1 01 01 29 Figure 11 Flow diagram LA1 4 24V AC DC ...