COMMISSIONING
14.1 COMMISSIONING WITH A DRY SENSOR
Switch on the mains voltage, the green LED of the electronic controller
LA1.1
or
LA1.4
lights up.
The liquid alarm control is ready to work!
In case the read alarm LED lights up, there is liquid on the sensor or there is a line break or you must
do an adjustment of the sensitivity (see chapter 14.3).
N O T E !
If the sensor is dry, the green LED indicates that the instrument is in
operating condition, the green LED is off when the red LED lights up
and signalizes a liquid alarm.
14.2 FUNCTION TEST
The response sensitivity of the
LA1S
and
LA25S
sensors should be checked during initial
commissioning and then twice a year as follows:
•
Disassemble sensor
LA1S
or
LA25S.
•
Short-circuit the sensor electrodes with a damp finger.
•
The electronic controller
LA1.1
or
LA1.4
indicates an alarm, i.e. the red LED lights up.
•
After the function test, dry the electrodes with a cloth.
•
Mount the sensor back into the mounting assembly.
For the
LA1S
and
LA25S
sensors, a cable break can be simulated by disconnecting a connection wire
from the electronic controller. Here, too, the electronic controller
LA1.1
or
LA1.4
must immediately
indicate an alarm, i.e. the LED must light up red.
N O T E !
If the alarm does not respond during the functional test, check the
sensor, electronic controller and connections.
N O T E !
The LA1S sensor can only detect condensate with a conductivity of
20 µS/cm or higher.
It is therefore advisable to check the function of the sensor with the
condensate that may be accumulated. To do this, remove the sensor
and carry out the function test described above with the
corresponding condensate.
Summary of Contents for LA Series
Page 26: ...26 LA 1 01 01 www mc techgroup com Figure 8 Flow diagram LA1 1 115 230 V 50 60 Hz ...
Page 27: ...www mc techgroup com LA 1 01 01 27 Figure 9 Flow diagram LA1 1 24V AC DC ...
Page 28: ...28 LA 1 01 01 www mc techgroup com Figure 10 Flow diagram LA1 4 115 230V 50 60Hz ...
Page 29: ...www mc techgroup com LA 1 01 01 29 Figure 11 Flow diagram LA1 4 24V AC DC ...