5
3.
Installation
3.1
Unpacking and inspection
1. Unpacking the UPS and check that whether it’s damaged during the
transportation. If damaged or some parts missing, don’t start the
machine and inform the carrier and franchiser.
2. Check the annex (please consult Appendix Table 1).
3. Check if the equipment is just what you wanted to purchase. You can affirm through
inspecting the model number on back panel of the equipment.
3.2
Notes
1. Please place the UPS in a clean, stable environment, avoid the vibration, dust, too
humidity, flammable gas and liquid, corrosive.
2. The ambient temperature around UPS should keep in a range of 0
℃~
40
℃
. If UPS
works above 40
℃
, it is required that the rated value of the largest load decreases
12
%
while the temperature increases every 5
℃
. The highest temperature cannot
be more than 50
℃
when UPS works.
3. UPS should be placed in a sufficiently ventilated place.
3.3
UPS input connection
Connect the UPS to the mains by input power cable which is equipped