MyPower VG2000 V4 VoIP Gateway Installation Manual
Page
62 / 72
When installing multiple devices on the same cabinet, install
the heavy devices at or near the bottom of the cabinet
without affecting the entire wiring and deployment. This can
reduce the cabinet center of gravity to improve stability.
When installing the device in the cabinet, it is recommended
to keep 1U space between two devices to ensure the heat
dissipation space for the device. Install the blank panel
configured for the cabinet in the space between two devices.
6.2.2 Grounding Requirement
The ground requirements for the upper bracket and device
with ground pole are as follows:
The ground mode should be in accordance with the
joint ground mode of the work ground, protection
ground, and building lightning protection ground
sharing the same ground body.
Ground line sectional area: ground line (sectional area
is determined by the possible passing maximum
current load. The ground line should adopt the good
conductor (copper) lead and cannot be deployed by the
naked lead. The resistance of the joint ground should
be less than 5
Ω
.)
6.2.3 Power Connection
MyPower VG2000-64S VoIP gateway adopts stable power
system. It has a low requirement for the input AC power.
Domestically, the AC standard for civil use is 220V and 50Hz.