13.2 Collektor sensor (Fault 1010, 2010, 3010)
Display:
[1010] Collektor BC
Description:
Collector sensor fracture, measuring circuit of collector sensor (X15) is open
Cause and Remedy:
Sensor not connected
►
Check and correct wiring
Sensor defect
►
Measure sensor (approx. 1,1k
Ω
at 77 °F), re-
place if required
Sensor cable defect
►
Replace sensor
Display:
[2010] Collektor SC
Description:
Measuring circuit of collector sensor (X15) is shorted out
Cause and Remedy:
Sensor defect
►
Measure sensor (approx. 1,1k
Ω
at 77 °F), re-
place if required
Sensor cable defect
►
Replace sensor
Display:
[3010] Collektor
Description:
Other fault at input X15
Cause and Remedy:
Sensor defect
►
Replace sensor
Sensor cable defect
►
Replace sensor
Input on heating controller
defect
►
Replace input on heating controller
Installation Manual AutoPellet Air Furnace 17 — 28
Summary of Contents for AutoPellet Air TOUCH 17
Page 42: ...42 Cable routing PE 603 USA_FA 1 0...
Page 43: ...Cable routing 43 Installation Manual AutoPellet Air Furnace 17 28...
Page 45: ...Wiring diagrams 45 Installation Manual AutoPellet Air Furnace 17 28...
Page 46: ...46 Wiring diagrams PE 603 USA_FA 1 0...
Page 47: ...Wiring diagrams 47 Installation Manual AutoPellet Air Furnace 17 28...
Page 70: ...70 Pellet Furnace cautionary markings PE 603 USA_FA 1 0...
Page 71: ...Pellet Furnace cautionary markings 71 Installation Manual AutoPellet Air Furnace 17 28...
Page 72: ...72 Pellet Furnace cautionary markings Labeling 105x74 PE 603 USA_FA 1 0...
Page 73: ...Pellet Furnace cautionary markings 73 Installation Manual AutoPellet Air Furnace 17 28...
Page 74: ......
Page 75: ......