Pump Configuration Fields
Blowback
- Blowback is a pulse of air to clear the filter. Blowback has two
configuration fields. Skip cycle defines the number of Bypass cycles skipped
between each blowback pulse. Default for Skip Cycle is 10. Setting Skip Cycle to
0 (zero) will pulse every time. Time Interval is a multiplication factor of 400ms to
pressurize the charge canister. Default Time Interval is 5 (1=400ms).
IDLE TIME
- The time in minutes that the pump runs after the last convey request
before shutting off.
BYPASS
- The time delay in 10ths of seconds (0-50, zero seconds to 5 seconds)
before the Bypass valve opens after all receivers are satisfied.
PURGE RATIO -
The % of time split between two purge valves. Used to clear
material that overshoots the receiver.
PUMP -
Selects between pump A or pump B outputs.
Press the info button to display the ID Number, Serial Number, firmware and the
label of the loader. From this screen the loaders label can be set or changed.
If info button is not displayed, press the image of the pump.
Summary of Contents for FLEXBUS
Page 2: ...M A G U I R E P R O D U C T S I N C 2 M A G U I R E FLEXBUS...
Page 22: ...M A G U I R E P R O D U C T S I N C 22 M A G U I R E FLEXBUS Flexbus Wiring Diagrams...
Page 23: ...M A G U I R E P R O D U C T S I N C 23 M A G U I R E FLEXBUS...
Page 24: ...M A G U I R E P R O D U C T S I N C 24 M A G U I R E FLEXBUS Flexbus Component Map...
Page 25: ...M A G U I R E P R O D U C T S I N C 25 M A G U I R E FLEXBUS Flexbus Lite Component Map...
Page 26: ...M A G U I R E P R O D U C T S I N C 26 M A G U I R E FLEXBUS...
Page 27: ...M A G U I R E P R O D U C T S I N C 27 M A G U I R E FLEXBUS...