10

 

 

 

It is recommended that only an authorized Magnum installer install your pellet/corn stove.

  The following installation 

guidelines must be followed to ensure conformity with both the safety listing of this stove and to local building codes. 

9

 

A listed 3” or 4” type “PL” pellet vent exhaust system must be used for FREESTANDING installation and attached to the 
pipe connector provided on the back of the stove.  Use a 3” to 4” adapter for 4” pipe.  A cap must be used at the 
termination of type “L” vent chimneys.  

It is recommended to use Corn Vent to assure long life of the venting. 

 

9

 

Do not terminate vent in any 

enclosed or semi-enclosed

 area, such as; carports, garage, attic, crawl space, under a sundeck 

or porch, narrow walkway or closed area, or any location that can build up a concentration of fumes such as a stairwell, 
covered breezeway, etc. 

 

9

 

Vent surfaces can get hot enough to cause burns if touched by children.  Non-combustible  shielding or guards may be 
required.  

Do not install a flue damper in the exhaust vent of this unit. 

 

9

 

Termination must exhaust above air inlet elevation. 

 It is recommended that at least 3 ft. of vertical pipe be installed 

when the appliance is vented directly through a wall or in a basement.

  This will create some natural draft to prevent 

the possibility of smoke or odor during appliance shutdown and to keep exhaust from causing a nuisance or hazard from 
exposing people or shrubs to high temperatures.  In any case, the safest and preferred venting method is to extend the vent 
through the roof.  

Do not connect this unit to a chimney flue serving another appliance. 

 

9

 

Distance from doors and windows, gravity or ventilation air inlet into building: 

Not less that 4 ft. / 1.2 m below, 4 ft. / 1.2 m horizontally from, 1 ft. / 305 mm above (This does not apply if the 
Windows are non-opening or have been fixed so they cannot open.) 

9

 

Distance from bottom of termination and grade – 1 ft. / 305 mm minimum.  This is conditional upon the plants and nature 
of grade surface.  The exhaust gases are not hot enough to ignite grass, plants or shrubs located in the vicinity of the 
termination.  The grade surface must not be a lawn.  Distance from bottom of termination and public walkway is 7ft. /2.1m 
minimum. 

 

9

 

Distance to combustible materials – 2 ft. / 610 mm.  This includes adjacent building, fences, protruding parts of the 
structure, roof overhang plants and shrubs, etc. 

 

9

 

It is recommended that a single or double clean-out “tee”, for cleaning the vent in both directions, be installed at every 90

junction

 

to enable collection of fly ash and to permit periodic cleaning of the exhaust system.  90

elbows accumulate fly- 

ash and soot thereby reducing exhaust flow and performance of the stove. 

 

9

 

Total length of horizontal vent must not exceed 10 feet  / 3,000 mm.  All joints in the vent system must be fastened by at 
least 3 screws, and all joints must be sealed with RTV silicone sealer to be airtight. 

 

9

 

A 3” single-wall, stainless steel flexible or rigid exhaust pipe should be used for INSERT installations and must be 
attached to the stove with a single-wall, stainless steel “tee” with a clean-out cap.  The stainless steel “tee” should be 
inclined at 45

0

 to enable the vent to be centered on the stove and allow the “tee” to be cleaned without removing the stove 

(see diagram ). 

 

9

 

When venting into an existing masonry or factory built chimney, the chimney must be cleaned, with all creosote removed.  
The chimney must be a type suited for solid fuel.  

WARNING:

 The chimney and the chimney connections must be kept 

clean and in good condition. 

 

9

 

The “PL” vent or single wall stainless exhaust system must be installed so as to be GAS TIGHT!  The vent manufacturer’s 
installation procedures must be followed.  In addition, pipe connections, joints and all pipe seams within the home should 
be sealed with high temperature RTV silicone sealer. 

 

9

 

If an insert is to be installed into an unlined masonry chimney, it is recommended that at 3” or 4” stainless steel pipe be 
extended to the top of the existing chimney.  The top of the existing chimney should be sealed with a steel plate (see 
diagram ). 

 

GUIDELINES FOR EXHAUST VENTING SYSTEMS DESIGN 

Summary of Contents for Baby Countryside Corn/ Biomass / Wood Pellet...

Page 1: ...roper venting practices must be followed Consult with a venting professional 9 Ashes must be disposed of in a metal container with a tight fitting lid 9 All minimum clearances to combustibles must be...

Page 2: ...1 Wiring Diagram AC DC 32 33 Draft Slide Gate Adjustment 34 Igniter Replacement 35 Trouble Shoot Guide 35 37 38 39 Magnum Replace Parts List 40 Warranty 41 Service Record 42 TESTING CERTIFICATION INFO...

Page 3: ...products is very much appreciated Many of our Dealers have referral rewards available and I encourage you to ask your local dealer how to get involved in helping make our country energy self sufficien...

Page 4: ...n the home It can be as simple as the air adjustment not set properly on the side of the stove or it could be that there is a serious lacking of good quality air in the home caused by negative pressur...

Page 5: ...5 make sure that there is nothing mechanical wrong with the appliance and then determine your need for proper fresh air Your dealer can contact the factory with any questions that he might have...

Page 6: ...fuels not approved for this appliance it will void the warranty and no service warranty will be allowed The Magnum models will burn high ash content fuels up to 5 but will require additional maintena...

Page 7: ...the proper dryness Check your Corn for foreign objects Your stove warranty will not cover damage done to your stove due to foreign objects in the fuel supply 9 Do not carry your corn supply over into...

Page 8: ...from supplier to supplier in ash content from less than 1 to 3 or more Low ash content pellets will allow you to burn the stove longer between cleanings Only wood pellets manufactured to the Associat...

Page 9: ...combustible material or equivalent extending beneath heater and to the front side rear as indicated CHIMNEY AND CONNECTOR 3 LISTED PELLET VENT ONLY NOTE REGARDLESS OF STOVE CLEARANCE VENT PIPE MUST AL...

Page 10: ...nature of grade surface The exhaust gases are not hot enough to ignite grass plants or shrubs located in the vicinity of the termination The grade surface must not be a lawn Distance from bottom of te...

Page 11: ...esponsible for Determining proper total equivalent pipe length depending on installation conditions Component Equivalent Length Equivalent Pipe Length Horizontal Straight Pipe Actual Length in ft x 1...

Page 12: ...equate fresh air to the home so that the Magnum appliance does not become the fresh air source 4 Only non combustible pipe 3 inches in diameter is approved to use for outside air connections straight...

Page 13: ...the stove and can be brought in through the sidewall or vented crawl space Flexible or rigid pipe should be used and will connect to the adaptor on the back of the stove See air inlet location under...

Page 14: ...be permanently bolted to the floor 2 Stove must have permanent outside air source 3 Stove must be permanently electrically ground to the steel chassis of the mobile home 12 ga or larger wire 4 All ve...

Page 15: ...er the pipe manufacturer s instructions Connect the pipe and lock the joints as directed by the pipe manufacturer and secure the vent pipe to the flue collar on the back of the stove Add a small bead...

Page 16: ...LANTS OR OTHER COMBUSTIBLES Note The pipe lengths shown are for reference only Your actual pipe length requirements may differ SINGLE WALL PIPE SHALL NOT BE USED FOR ANY INSTALLATION HORIZONTAL INSTAL...

Page 17: ...es and presence of all necessary parts including a chimney cap prior to making the connection 3 This stove may be connected to an existing ceiling mounted factory built chimney with a diameter of 4 6...

Page 18: ...s ash buildup premature failure of exhaust system staining of the house siding and serious creosote buildup This installation should not be used in a cold climate area Storm Collar Note This type of i...

Page 19: ...back of the control panel When the room temperature drops below the thermostat setting the thermostat switch will close allowing the stove to operate at the medium or higher settings When the room tem...

Page 20: ...two terminals on the back of the control panel When the room temperature drops below the thermostat setting the thermostat switch will close allowing the stove to operate at the medium or higher setti...

Page 21: ...terminal 10 Reconnect the 110 volt AC power The stove is now ready for 12 volt back up and will switch automatically to 12 volt operation when AC power is lost When AC power is restored the stove will...

Page 22: ...uger will stop feeding and You will need to start the cycle over again Pushing and holding the Auger switch allows you to prime the auger and add fuel to the firepot automatically This can be done app...

Page 23: ...ger and add fuel to the firepot automatically This can be done app 1 minute after pushing the on off start button The unit starts automatically on the low heat setting When you have started the unit a...

Page 24: ...r settings An air damper closed too much will produce a lazy and slow flame Adjusted properly the flames should be bright and lively Altitude and fuel types greatly affect the amount of air required O...

Page 25: ...ME VACUUM CLEANERS ALLOW ASH TO ESCAPE INTO THE ROOM AIR HOWEVER VACUUMING IS RECOMMENDED OCCASIONALLY TO AID IN SEASONAL CLEANING AND KEEP THE UNIT FREE OF EXCESS ASH DISCARD THE VACUUM BAG AFTER EAC...

Page 26: ...they should be inspected and vacuumed clean The combustion blower is accessed by opening the stove s right side panel and then removing the inspection caps or the exhaust manifold cover See figure bel...

Page 27: ...spected cleaned GASKETS INSPECTED Inspected or replaced DOOR GLASS CLEANED INSPECTED V CHIMNEY CLEANING A Creosote Formation Any time a wood or Biomass product is burned slowly tar and other bi produc...

Page 28: ...mproper make up air for the home improper venting or failure to clean the 3 exhaust in the stove will cause the pressure switch to shut off the fuel feed To resume operation it is necessary to locate...

Page 29: ...e sure that the glass is not sitting on top of any obstruction The glass will break when tightening the screws if the glass is on the gasket Hold the glass toward the top of the door glass channel whe...

Page 30: ...hest setting Optimum efficiency is achieved by using lower settings 2 or 3 It is also recommended that the unit not be run for extended periods of time on the number 1 setting The draft blower and ven...

Page 31: ...s with the ability to use 3 separate programming features This programming must be done by a qualified factory trained technician Contact your local dealer to set up an appointment to have this done T...

Page 32: ...l will build up in the firepot and eventually smother the flame If this happens or if you notice the firepot is filling up with partially burned fuel open the damper 1 8 at a time until the fire is cl...

Page 33: ...33 AC MODEL WIRING DIAGRAM WARNING DISCONNECT POWER BEFORE SERVICING THIS UNIT DC MODEL DDC 3000 WIRING DHC 3000 AC board...

Page 34: ...34 DIAGRAM WARNING DISCONNECT POWER BEFORE SERVICING THIS UNIT...

Page 35: ...s adjustment must be made by a qualified Magnum Service Tech When rotating the slide gate be careful not to damage the gasket Re tighten the bolts and check for leaks The Draft Slide Gate is not shipp...

Page 36: ...he threads Do not over tighten the igniter assembly If you over tighten the igniter assembly it may ruin the igniter Crimp on the terminal ends and attach the terminal ends onto the wiring harness If...

Page 37: ...access plates 9 Change to a better grade of fuel if necessary 9 Check that damper control knob is adjusted properly Pull out to increase fire burn 9 Push ash cleanout slides in 9 Check gasket seal ar...

Page 38: ...l is dirty or wet Auger circuit board pressure switch or relay 9 Check contents of the hopper Add fuel if necessary 9 Check all operation fuses re set manual high limit thermodisk 9 Clean out auger sy...

Page 39: ...house 9 Clean the glass when the unit is not running 9 Seal any leaks in the exhaust system with RTV high temperature silicone sealer 9 Use approved ash Vacumm 9 Correct negative pressure situation 9...

Page 40: ...o much ash Dirty fuel Wet fuel Lack of clean combustion air Dirty or plugged stove or venting Poor exhaust vent configuration Negative pressure present in the home Combustion motor going out Use combu...

Page 41: ...y Countryside T40 Essex Hopper Pressure Switch 42 RP2063 Magnum Baby Countryside AC unit Wire Harness assembly 58 RP2062 Magnum Baby Countryside DC unit Wire Harness assembly 58 RP2075 Magnum Baby Cou...

Page 42: ...efective part The sole duty of the Manufacturer and liability under this warranty is limited to the repair or replacement of the covered defective part The purchaser shall assume all costs related to...

Page 43: ...43 SERVICE RECORD DATE SERVICE OR CLEANING PERFORMED This record must be sent in when any warranty claims are made...

Reviews: