48
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
Priority
Indicator Name
Default
Category
Explanation
Remedy
10
Sweep Time Error
Failure
Internal Timing Error
Contact Magnetrol Technical Support
11
Spare Indicator 3
OK
Reserved for future use
12
Too Many Echoes
Failure
Excessive number of possible echoes
detected
Check settings:
Dielectric Range
Sensitivity
Polarization Direction
View Echo Curve.
13
Safety Zone Alarm
Failure
Risk of echo loss if liquid rises above
Top Blocking Distance
Ensure that liquid cannot reach
Blocking Distance
14
Echo Lost
Failure
No detectable level signal identified
within the configured range
Check settings:
Dielectric Range
Sensitivity
Tank Height
View Echo Curve
15
Spare Indicator 4
OK
Reserved for future use
16
Spare Indicator
11
OK
Reserved for future use
17
High Volume Alarm
Failure
Volume calculated from Level reading
exceeds capacity of vessel or custom
table
Check settings:
Vessel Dimensions,
Custom Table entries
18
High Flow Alarm
Failure
Flow calculated from Distance reading
exceeds capacity of flow element or
custom table
Check settings:
Flow Element,
Reference Distance
Gen Eqn Factors
Custom Table entries
19
Spare Indicator 5
OK
Reserved for future use
20
Initializing
Function
Check
Distance measurement is inaccurate
while internal filters are settling
Wait for up to 10 seconds
21
TB Config Changed
Function
Check
A parameter has been modified from the
User Interface
If desired, reset Config Changed
indicator in ADVANCED CONFIG
22
Spare Indicator 6
OK
Reserved for future use
23
High Elec Temp
Out of
Spec
Electronics too hot. May compromise
Distance measurement or damage
instrument
Shield transmitter from heat source or
increase air circulation
24
Low Elec Temp
Out of
Spec
Electronics too cold. May compromise
Distance measurement or damage
instrument
Insulate transmitter or locate remotely
in a warmer area