28
IN_LO
: Input of the low range transmitter, in a range
extension application.
IN–1, IN–2, IN–3
: Inputs combined with the PV in a
section of four term math functions.
RANGE_HI
: Constant value above which the range exten-
sion has switch to the high range transmitter.
RANGE_LO
: Constant value below which the range exten-
sion has switch to the high range transmitter.
BIAS_IN_1
: The bias value for IN_1.
GAIN_IN_1
: The proportional gain (multiplier) value for
IN_1.
BIAS_IN_2
: The bias value for IN_2.
GAIN_IN_2
: The proportional gain (multiplier) value for
IN_2.
BIAS_IN_3
: The bias value for IN_3.
GAIN_IN_3
: The proportional gain (multiplier) value for
IN_3.
COMP_HI_LIM
: Determines the high limit of the com-
pensation input.
COMP_LO_LIM
: Determines the low limit of the com-
pensation input.
ARITH_TYPE
: The set of nine arithmetic functions
applied as compensation to or augmentation of the range
extended input.
BAL_TIME
: Specifies the time for a block value to match
an input, output, or calculated value or the time for dissipa-
tion of the internal balancing bias.
BIAS
: The bias value is used to calculate the output.
GAIN
: The gain value is used to calculate the output.
OUT_HI_LIM
: The maximum output value allowed.
OUT_LO_LIM
: The minimum output value allowed.
UPDATE_EVT
: This alert is generated by any changes to
the static data.
BLOCK_ALM
: Used for all configuration, hardware, con-
nection failure, or system problem in the block.
BLOCK_ERR_DESC
: Reports more specific details regard-
ing some errors reported through BLOCK_ERR.
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual