11
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
WRITE_LOCK
: When set to LOCKED, will prevent any
external change to the static or non-volatile data base in the
Function Block Application of the transmitter. Block con-
nections and calculation results will proceed normally, but
the configuration will be locked.
UPDATE_EVT (Update Event)
: Is an alert generated by a
write to the static data in the block.
BLOCK_ALM (Block Alarm)
: Is used for configuration,
hardware, connection, or system problems in the block. The
cause of any specific alert is entered in the subcode field.
ALARM_SUM (Alarm Summary)
: Contains the current
alert status, the unacknowledged states, the unreported
states, and the disabled states of the alarms associated with
the block.
ACK_OPTION (Acknowledge Option)
: Selects whether
alarms associated with the block will be automatically
acknowledged.
WRITE_PRI (Write Priority)
: The priority of the alarm
generated by clearing the write lock.
WRITE ALM (Write Alarm)
: The alert generated if the
write lock parameter is cleared.
ITK_VER (ITK Version)
: Contains the version of the
Interoperability Test Kit (ITK) used by the FieldComm
Group during their interoperability testing.
2.2.2 Additional Resource Block Parameters
Additional parameters are available within the resource
block for use with NE-107 to aid in communicating device
conditions to the user.
FD_VER
: Major version of the Field Diagnostic specifica-
tion to which this device conforms.
FD_FAIL_ACTIVE
: For error conditions that have been
selected for the FAIL alarm category, this parameter reflects
those that have been detected as active.
FD_OFFSPEC_ACTIVE
: For error conditions that have
been selected for the OFFSPEC alarm category, this para-
meter reflects those that have been detected as active.
FD_MAINT_ACTIVE
: For error conditions that have been
selected for the MAINT alarm category, this parameter
reflects those that have been detected as active.
FD_CHECK_ACTIVE
: For error conditions that have
been selected for the CHECK alarm category, this parameter
reflects those that have been detected as active.