30
58-641 PULSAR Model R86 Pulse Burst Radar Transmitter - F
OUNDATION
fieldbus
™
Instruction Manual
IN_2
: The block input value and status.
IN_3
: The block input value and status.
IN_4
: The block input value and status.
DISABLE_1
: Parameter to switch off the input from being
used 0- Use, 1 - Disable.
DISABLE_2
: Parameter to switch off the input from being
used 0- Use, 1 - Disable.
DISABLE_3
: Parameter to switch off the input from being
used 0- Use, 1 - Disable.
DISABLE_4
: Parameter to switch off the input from being
used 0- Use, 1 - Disable.
SELECT_TYPE
: Determines the selector action; First
good, Minimum, Maximum, Middle, Average.
MIN_GOOD
: The minimum number of inputs which are
“good” is less than the value of MIN_GOOD then set the
OUT status to “bad”.
SELECTED
: The integer indicating the selected input
number.
OP_SELECT
: An operator settable parameter to force a
given input to be used.
UPDATE_EVT
: This alert is generated by any change to
the static data.
BLOCK_ALM
: The block alarm is used for all configura-
tion, hardware, connection failure, or system problems in
the block.
BLOCK_ERR_DESC
: Reports more specific details regard-
ing some errors reported through BLOCK_ERR.
3.4
Signal Characterizer Block (SC)
The Signal Characterizer (SC) function block characterizes
or approximates any function that defines an input/output
relationship. The function is defined by configuring as
many as 21 X, Y coordinates. The block interpolates an out-
put value for a given input value using the curve defined by
the configured coordinates. Two separate analog input sig-
nals can be processed simultaneously to give two corre-
sponding separate output values using the same defined
curve.
ST_REV
: The revision level of the static data associated
with the function block. The revision value will be incre-
mented in each time a static parameter value in the block is
changed.