13
FD_EXTENDED_ACTIVE_1
: For error conditions that
have been selected in the Extended_Map_1 parameter, this
parameter reflects those that have been detected as active.
FD_EXTENDED_MAP_1
: Allows the user finer control
in selecting multiple conditions contributing to a single
condition that may be mapped for the various alarm cate-
gories.
Manufacturer-Specific Parameters:
SOFT_SIMULATION_DISABLE
: If set to yes, enabling
of simulation is disallowed regardless of the presence of the
simulation jumper, and the “simulation” indicator will be
cleared in the Block Error parameter. If set to no, simula-
tion can only be enabled if the simulation jumper is present
which also sets the “simulation” indicator in the Block Error
parameter.
SERIAL_NUMBER
: Read-only parameter that corresponds
to “Magnetrol Serial Number” in the Transducer Block.
FIRMWARE_VERSION
: Read-only parameter that corre-
sponds to “Firmware Version” in the Transducer Block.
HARDWARE_VERSION
: Read-only parameter that corre-
sponds to “Hardware Version” in the Transducer Block.
2.3 Transducer Block
The three TRANSDUCER blocks (TB) contained within
the ECLIPSE Model 706 FF transmitter are custom blocks
containing parameters that are pertinent to the transmitter
itself.
TRANSDUCER Block 1 (used for level and interface oper-
ation) contains information such as the Configuration,
Diagnostics, Calibration data, output level and Status infor-
mation.
TRANSDUCER Blocks 2 and 3 contain volume and flow
parameters respectively.
The read-only parameters and read-write parameters within
the TB are grouped in a useful configuration.
• The read-only parameters report the block status and
operation modes.
• The read-write parameters affect both the operation of
the function block and the transmitter itself.
NOTE: The Transducer Block will automatically be changed to “Out of
Service” when the local interface (keypad) is used to change a
static parameter online. The Transducer Block must be manually
placed back in service from the Host System to resume
operation.
BE57-646 ECLIPSE Guided Wave Radar Transmitter - F
OUNDATION
fieldbus
™