52
BE57-646 ECLIPSE Guided Wave Radar Transmitter - F
OUNDATION
fieldbus
™
diagnostic/Condition
Process Variables
Quality
Sub-status
Limit
No Echoes
All PVs except
Elec Temperature
Bad
Sensor Failure
Constant limited
Lvl Below ProbeEnd
All PVs except
Elec Temperature
Bad
Sensor Failure
Constant limited
EoP Below ProbeEnd
All PVs except
Elec Temperature
Bad
Sensor Failure
Constant limited
Software Error
All PVs
Bad
Device Failure
Constant limited
RAM Error
All PVs
Bad
Device Failure
Constant limited
ADC Failure
All PVs
Bad
Device Failure
Constant limited
EEPROM Error
All PVs
Bad
Device Failure
Constant limited
No Fiducial
All PVs except
Elec Temperature
Bad
Device Failure
Constant limited
Echo Lost
All PVs except
Elec Temperature
Bad
Device Failure
Constant limited
Inferred Level
Echo Strength
Ifc Level
Upper Thickness
Ifc Echo Strength
Probe Buildup
Bad
Device Failure
Constant limited
Totalizer Data Lost
NR Totalizer
R Totalizer
Bad
Config Error
Not limited
Default Parameters
All PVs
Bad
Config Error
Not limited
EoP Above ProbeEnd
All PVs except Elec
Temperature
Bad
Config Error
Not limited
Buildup Detection
disabled
Probe Buildup
Bad
Config Error
Constant limited
MeasType !=
Interface & Level
Ifc Level
Upper Thickness
Ifc Echo Strength
Bad
Config Error
Constant limited
MeasType !=
Volume & Level
Volume
Bad
Config Error
Constant limited
MeasType != Flow
Flow
Head
NR Totalizer
R Totalizer
Bad
Config Error
Constant limited
MeasType = Flow and
R Totalizer Mode off
R Totalizer
Bad
Config Error
Constant limited
High Volume Alarm
Volume
Bad
Config Error
High limited
High Flow Alarm
Flow
Head
Bad
Non-Specific
High limited
Safety Zone Alarm
Level
Ifc Level
Upper Thick
Distance
Volume
Head
Flow
Bad
Non-Specific
Not limited