20
BE57-646 ECLIPSE Guided Wave Radar Transmitter - F
OUNDATION
fieldbus
™
2.4.4 aI Block Configuration
Below are shown some examples of various typical AI Block
configurations.
Probe
PL [in / cm]
Probe Length = PL Inches or cm
Transducer
Block +
LCD Level
AI Block Output
[To FF segment]
100%
0 [in / cm]
0%
Probe
Probe
Length
111 cm
81.3 cm
0 cm
100%
0%
Offset = –15.5 cm
Transducer
Block +
LCD Level
AI Block Output
[To FF segment]
Configuration
Probe Length
111
Level Offset
-15.5
XD Scale EU at 0%
0
XD Scale EU at 100%
81.3
XD Scale Units
cm
Out Scale EU at 0%
0
Out Scale EU at 100%
100
Out Scale Units
%
L Type
Indirect
Configuration
Probe Length
111
Level Offset
-15.5
XD Scale EU at 0%
0
XD Scale EU at 100%
81.3
XD Scale Units
cm
Out Scale EU at 0%
0
Out Scale EU at 100%
81.3
Out Scale Units
cm
L Type
Direct
Probe
Probe
Length
111 cm
81.3 cm
0 cm
81.3 cm
0 cm
Offset = –15.5 cm
Transducer
Block +
LCD Level
AI Block Output
[To FF segment]
Configuration
Probe Length
PL
Level Offset
0
XD Scale EU at 0%
0
XD Scale EU at 100%
PL
XD Scale Units
in/cm
Out Scale EU at 0%
0
Out Scale EU at 100%
100
Out Scale Units
%
L Type
Indirect
Example 1
: standard
configuration for trans-
mitter with probe of
length PL inches or cm.
[setup by factory as
part of final assembly
procedure]
Example 2
: end user desires 0 to
100% output for a subset of the
measureable region [probe]
[e.g., for a chamber application]
Example 3
: same configuration as
previous except Direct [no] scaling
setup in AI block
Output to FF segment is in cm