The stall prevention/current limit level during acceleration is set as a percentage of inverter rated
current. During acceleration, if the output current exceeds this current limit level (L3-02),
acceleration stops and frequency is maintained. When the output current decreases below this
current level (L3-02), acceleration resumes. See Figure 5-7 below.
*Controls the acceleration rate to prevent the inverter from tripping.
Figure 5-7: Stall Prevention/Current Limit During Acceleration
Time
Frequency Output
*
Time
Motor Current
*
Controls the acceleration rate to
L3-02
Summary of Contents for Impulse-t 2006-T
Page 2: ......
Page 7: ...C h a p t e r 1 Introduction...
Page 8: ...IMPULSE T Instruction Manual October 2015 1 2 This page intentionally left blank...
Page 14: ...IMPULSE T Instruction Manual October 2015 1 8 This page intentionally left blank...
Page 15: ...C h a p t e r 2 Installation...
Page 16: ...IMPULSE T Instruction Manual October 2015 2 2 This page intentionally left blank...
Page 21: ...C h a p t e r 3 Wiring...
Page 22: ...IMPULSE T Instruction Manual October 2015 3 2 This page intentionally left blank...
Page 33: ...C h a p t e r 4 Getting Started...
Page 34: ...IMPULSE T Instruction Manual October 2015 4 2 This page intentionally left blank...
Page 44: ...IMPULSE T Instruction Manual October 2015 4 12 This page intentionally left blank...
Page 45: ...C h a p t e r 5 Programming Features...
Page 46: ...IMPULSE T Instruction Manual October 2015 5 2 This page intentionally left blank...
Page 69: ...C h a p t e r 6 Troubleshooting...
Page 70: ...IMPULSE T Instruction Manual October 2015 6 2 This page intentionally left blank...
Page 77: ...A p p e n d i x A Advanced Parameter Listing...
Page 78: ...IMPULSE T Instruction Manual October 2015 A 2 This page intentionally left blank...