IMPULSE•T Instruction Manual – October 2015
5-14
External Fault Response Selection
It is sometimes desirable to have at least one external fault input to the drive. To properly program a
multi-function input (H1-01 to H1-05), an external fault response must be selected. The table below
shows the possible selections for an external fault response.
Table 5-17:External Fault Response Selection
(1) N.O. = normally open contact; N.C. = normally closed contact
External Fault Selection
Input Level
Selection
Detection Method
External Fault Action
MFI Setting
Result
N.O.
(1)
N.C.
(1)
Always
During
Run
Ramp to
Stop
Coast to Stop
Alarm
Only
20
24
28
2C
22
26
2A
2E
21
25
29
2D
23
27
2B
2F
Summary of Contents for Impulse-t 2006-T
Page 2: ......
Page 7: ...C h a p t e r 1 Introduction...
Page 8: ...IMPULSE T Instruction Manual October 2015 1 2 This page intentionally left blank...
Page 14: ...IMPULSE T Instruction Manual October 2015 1 8 This page intentionally left blank...
Page 15: ...C h a p t e r 2 Installation...
Page 16: ...IMPULSE T Instruction Manual October 2015 2 2 This page intentionally left blank...
Page 21: ...C h a p t e r 3 Wiring...
Page 22: ...IMPULSE T Instruction Manual October 2015 3 2 This page intentionally left blank...
Page 33: ...C h a p t e r 4 Getting Started...
Page 34: ...IMPULSE T Instruction Manual October 2015 4 2 This page intentionally left blank...
Page 44: ...IMPULSE T Instruction Manual October 2015 4 12 This page intentionally left blank...
Page 45: ...C h a p t e r 5 Programming Features...
Page 46: ...IMPULSE T Instruction Manual October 2015 5 2 This page intentionally left blank...
Page 69: ...C h a p t e r 6 Troubleshooting...
Page 70: ...IMPULSE T Instruction Manual October 2015 6 2 This page intentionally left blank...
Page 77: ...A p p e n d i x A Advanced Parameter Listing...
Page 78: ...IMPULSE T Instruction Manual October 2015 A 2 This page intentionally left blank...