3
E1-11 thru
E1-13
V/F Mid. Output Freq., Mid.
Output Voltage, and base voltage
Not normally adjusted.
Leave at default.
Used to set constant
horsepower area of V/F
curve.
E2-01
Motor Rated Full Load Amps
Set to motor rated
current
Enter motor rated
current.
E2-04
Number of Motor Poles
2 to 48
For a 50 Hz motor:
Rated RPM No. of Poles
3000
2
1500
4
1000
6
750
8
600
10
E2-11
Motor Rated Output (KW)
Set to motor rated
kilowatts/2
Actual voltage is twice
what is entered so
power is double also.
F1-01
PG Parameter
n/a
Sets number of pulses
per revolution of
encoder.
Note: Parameters may need to be adjusted for specific application and motor configuration.