GP1000
Quick Start Guide
C
ONFIGURE
H
ARDWARE
1. DC Bus Enable
a. To configure the drive so the DC Bus charges up when power is applied place a jumper
between TB9-1 and TB9-2.
b. To configure the drive so the DC Bus charges up on demand place a switch between
TB9-1 and TB9-2.
2. Filter Inductor
a. The DC Bus Filter Inductor should be connected between 1+ and 2+.
b. To run without an inductor (not recommended) place a conductor sized to carry 100
Arms between terminals 1+ and 2+.
3. Liquid Cooling
a. Supply each of the two heat sinks with 1 gallon per minute (3.8 Litres per minute)
coolant flow at a maximum inlet coolant temperature of 60 C.
b. If the heat sinks are connected in series it is preferred that the IGBT heat sink receive
liquid from the chiller and the rectifier heat sink receive liquid from the IGBT heat sink
outlet.
C
ONFIGURE
P
ARAMETERS
Parameters that need to be entered into the drive via the keypad for V/f control mode are
:
PARAMETER DESCRIPTION
VALUE
EFFECT
A1-02
Control Method
0
Sets drive to operate as
V/F without encoder
(PG)
B1-01
Frequency Reference Source
0
Frequence reference set
to operator input.
B1-02
Run Command Source
0
Selects operator as run
command input source.
B1-03
Stopping Method
1
Selects stopping method
when “run” command is
removed to be “coast to
stop.”
C1-01
Acceleration Time
10
Sets the acceleration
time to 10 seconds
C1-02
Deceleration Time
n/a
Not applicable if B1-03
is set to 1.