Using Pulse Train Monitor Contents
This section explains pulse monitor parameters.
Related Parameters
Selecting Pulse Monitor Items
Output digital operator monitor items (U1-
[status monitor]) from pulse monitor terminal MP-SC. Refer to
, and set the
part of U1-
(Status monitor). The possible monitor selections
are limited as follows: U1-01, 02, 05, 20, 24, 36.
Adjusting the Pulse Monitor Items
Adjust the pulse frequency output from pulse monitor terminal MP-SC. Set the pulse frequency output when
100% frequency is output to H6-07.
Set H6-06 to 2, and H6-07 to 0, to output the frequency synchronous with the Drive's U-phase output.
Application Precautions
When using a pulse monitor parameter, connect a peripheral device according to the following load condi-
tions. If the load conditions are different, there is a risk of characteristic insufficiency or damage to the
machinery.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
H6-06
Terminal MP
Pulse Train
Monitor
Selection
Select the pulse train monitor output
terminal MP function (value of the
xx part of U1-xx). See Table A2 for
the list of U1 monitors.
1, 2, 5,
20, 24,
31, 36
only
2
Yes
A
A
A
A
A
Pulse Output
Sel
H6-07
Pulse Train
Monitor
Scaling
Sets the number of output pulses
when the monitor is 100% (inHz).
Set H6-06 to 2, and H6-07 to 0, to
make the pulse train monitor output
synchronous to the output
frequency.
0
to
32000
1440Hz
Yes
A
A
A
A
A
PO Scaling
Using a Sourcing Output
Output Voltage
(Isolated)
VRL (V)
Load Impedance (k
)
+5V min.
1.5 k
min.
+8V min.
3.5 k
min.
+10V min.
10 k
min.
Load impedance
MP
AC
VRL