Delta-T Menu
Parameter Function Description
Garda
18
Garda
21
Garda
28
U.M
D01
Stabilization Delta
10
15
°C
D04
Fume Delta-T for automatic calibration of Warm Air Fan
20
20
°C
D05
Ambient Delta-T for automatic calibration of Warm Air Fan
10
10
°C
D08
Water Delta-T for combustion automatic calibration
8
8
°C
D23
Delta to be added to Boiler Thermostat to switch from
Modulation to Standby at the end of T43 and if A13=1 or 2
8
8
°C
D41
Power-up Delta
8
8
°C
Pressure Sensor Thresholds Menu
Parameter Function Description
Garda
18
Garda
21
Garda
28
U.M
SP01
Sensor Pressure Minimum Threshold for water in the boiler
300
300
300
mbar
SP08
Sensor Pressure Maximum Threshold for water in the boiler
2300
2300
2300
mbar
Meter Menu
Submenu
Meter Description
Total Hours
Power supply Total Time
Hours of operation
Operation time: time in which at least one fan runs
Hours in Normal mode
Actual heating times in Normal work or Modulation mode
No. of ignitions
Number of successful ignition attempts
No. of unsuccessful
ignitions
Number of successful ignition attempts
No. of errors
Number of errors occurred
Meter reset
Reset all meters: reset all meters to zero
Output Test Menu
Menu that allows testing individual outputs of circuit board (and, therefore, loads connected to
it) with the system in Off mode. If outputs are active, they will automatically switch off after 30
seconds.
Submenu
Description
Fume extractor
Fume extractor test
Output V2
Output V2 test
Auger
Auger test
Glowplug
Glowplug test
Output P/V3
Output P/V3 or Warm Air Fan, if supplied
Output Aux1
Output Aux1 or motorized valve test, if required
Pump 1
Pump1 test