background image

506326-01

Page 9  of  20

Issue 0941

Air Filter

All indoor return air must be filtered. A washable filter is
furnished with the unit, located in the return air opening.
Provisions must be made to accommodate filter servicing.

The filter should be cleaned at least three times during each
of the heating and cooling seasons, or more frequently if
unusual conditions are encountered. To clean the washable
filter, shake filter to remove excess dirt
and/or use a vacuum cleaner. Wash filter in soap or detergent
water and replace after filter is dry. It is not necessary to oil
the filter after washing.

If an installation is made in which it is more desirable to
mount the filter exterior to the unit, in the return duct work or
elsewhere, the washable filter can be used or replaced with
a disposable filter. If a disposable filter is used, use the
information provided in Table 4 when sizing the disposable
filter.  These units are not designed for high static filtration.

Condensate Drain

Provisions must be made to properly drain the indoor and
outdoor drain pans of this appliance.

The indoor drain pan drains internally into the outdoor drain.
The outdoor drain connection is a 3/4" NPT to 3/4" PVC fitting
(schedule 40 minimum).  The drain size should not be reduced.
The drain must be trapped as shown in Figure 7.  The drain
line should pitch gradually downward at least 1" per 10' of
horizontal run to open drain.

Electrical Connections

All wiring must be done in accordance with the National
Electrical Code (NEC), ANSI/NFPA No. 70 (latest edition);
Canadian Electrical Code CSA C22.2 Part 1 (latest edition);
or local codes, where they prevail.  Any alteration of internal
wiring will void certification and warranty.  Units are factory
wired for a 230 volt single phase power supply.  If power
supply is 208 volts, it will be necessary to change a wire
connection on unit transformer from 240 volt terminal to 208
volt terminal as shown on the wiring diagram.

Use wiring with a temperature limitation of 75°C minimum.
Run the 208 or 230 volt, 60 hertz electric power supply
through a fused disconnect switch to the control box of the
unit and connect as shown in the wiring diagram located on
the inside of the control access panel.

The unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the
National Electrical Code ANSI/NFPA No. 70 (latest edition)
or CSA C22.2 Part 1 (latest edition).

Power supply to the unit must be NEC Class 1 and must
comply with all applicable codes.  A fused disconnect switch
should be field provided for the unit.  The switch must be
separate from all other circuits. If any of the wire supplied
with the unit must be replaced, replacement wire must be of
the type shown on the wiring diagram.

Electrical wiring must be sized to minimum circuit ampacity
marked on the unit.  

Use copper conductors only.  

Each

unit must be wired with a separate branch circuit and be
properly fused.

Figure 7

Condensate Drain Installation

Use thread sealant on the threaded fittings. Install
threaded fittings by hand only.  

Do not overtorque the

fittings.

 CAUTION

Minimum Required Surface Area

for Disposable Filters

Table 4

*  9 and 10 EER models

Model Number

Filter Area

MGE*12

MGE*18

MGE*24

MGE*30-36

192 Square Inches

288 Square Inches

384 Square Inches

480 Square Inches

Summary of Contents for MGE4-09-18

Page 1: ...installation of this appliance must conform to the requirements of the National Fire ProtectionAssociation the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadia...

Page 2: ...ice required Refer to Table 1 for the application limitations of the unit Location For information on wall sleeves and grille accessories see ACCESSORIES on page 17 The design is certified for thru th...

Page 3: ...on the unit and as tall as the unit IMPORTANT The unit must be installed with approved wall sleeve and grille accessories for safe operation Improper installa tions could result in property damage per...

Page 4: ...with appropriate wall sleeve accessories There is no minimum clearance required on locating the unit to an interior corner of a building If the unit is installed in a residential garage it must be loc...

Page 5: ...monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the common vent...

Page 6: ...all sleeve make sure that the proper louver kit is installed Due the high temperatures of the combustion products released from the gas vent MGE gas package units require the use of either an aluminum...

Page 7: ...unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America ACCA Check unit air supply outle...

Page 8: ...Low High MGE4 09 24 Low Medium Low Medium High Medium High High 650 630 610 580 550 500 470 435 390 370 670 640 575 520 460 750 690 645 575 490 795 740 680 616 535 945 900 860 810 775 1010 960 910 870...

Page 9: ...al Code CSA C22 2 Part 1 latest edition or local codes where they prevail Any alteration of internal wiring will void certification and warranty Units are factory wired for a 230 volt single phase pow...

Page 10: ...in the gas line outside the unit 5 above the floor or in accordance with any local codes The furnace must be isolated from the gas supply piping system by closing the individual manual shutoff valve d...

Page 11: ...dures Color coded insulated wires minimum 18AWG should be used to connect the thermostat to the unit The gas valve supplied with this furnace is rated at 1 2 psig maximum Any higher pressure may ruptu...

Page 12: ...er the pre purge time expires burners will light For Your Safety Read Before Lighting To Shut Down Unit 1 Turn off electrical power to unit 2 Depress and turn the gas valve knob to the OFF position se...

Page 13: ...r temporary or short periods of shutdown set the thermostat system switch to OFF For a prolonged period of shutdown set the thermostat system switch to OFF and turn off the electrical power supply and...

Page 14: ...ation Continuousoperationoftheairhandlingblowerwillbeobtained if the thermostat fan switch is set to ON With the thermostat fan switch set to AUTO the air handling blower will cycle corresponding with...

Page 15: ...5 To adjust the manifold pressure refer to previous section Checking andAdjusting Gas Input on page 13 For installations above 7500 feet refer to the National Fuel Gas Code Installation and Operation...

Page 16: ...tion control 3 Remove ignitor and flame sensor 4 Remove the four screws that mount the burner right side plate houses the ignitor flame sensing rod 5 Carefully remove the burner right side plate 6 Bur...

Page 17: ...2 6 Wall Sleeve Kit 6 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE8 1 ASLEEVE8 2 8 Wall Sleeve Kit 8 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE10 1 ASLEEVE10 2 10 Wall Sleeve Kit 10 Wall Sleeve Ki...

Page 18: ...V E E L S A 8 5 4 8 1 5 4 8 1 9 2 4 8 E V E E L S A 1 0 1 E V E E L S A 0 1 9 2 8 1 9 2 8 1 9 2 2 0 1 E V E E L S A 0 1 4 3 2 3 8 7 2 3 8 1 9 2 3 0 1 E V E E L S A 0 1 5 4 8 1 5 4 8 1 9 2 4 0 1 E V E...

Page 19: ...506326 01 Page 19 of 20 Issue 0941 Figure 10 Connection Diagram...

Page 20: ...Page 20 of 20 506326 01 Issue 0941 Figure 11 Schematic...

Reviews: