background image

Page 10  of  20

506326-01

Issue 0941

Gas Supply and Piping

Refer to unit rating plate to make sure the furnace is equipped
to burn the gas supplied (natural or propane).

Gas supply piping should be installed in accordance with
local codes and the regulations of the utility.  Piping must be
of adequate size to prevent undue pressure drop.  Consult
the local utility or gas supplier for complete details on special
requirements for sizing gas piping.

If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector.  Do not use a
connector which has previously serviced another gas
appliance.

Pipe connections must be tight, and a non-hardening pipe
compound resistant to liquefied petroleum gases must be
used.

Connect the gas pipe to the furnace controls providing a
ground joint union as close to the controls as is possible to
facilitate removal of controls and manifold.  Provide a drip
leg on the outside of the furnace.  A manual shutoff valve
shall be installed in the gas line, outside the unit, 5' above
the floor, or in accordance with any local codes.

The furnace must be isolated from the gas supply piping
system by closing the individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressure equal to or less than 1/2 psig (3.5 kPa) or 14" W.C.
If the piping system is to be tested at pressures in excess of
1/2 psig (3.5 kPa), the furnace and its appliance main gas
valve must be disconnected from the gas supply piping
system.

Any conversion of a natural gas unit to propane gas must
be done by qualified personnel using a conversion kit
available from the manufacturer, following the instructions
in the conversion kit.  If done improperly, overfiring of the
burners and improper burner operation can result.  This
can create carbon monoxide which could cause
asphyxiation.

  WARNING

Figure 8

Gas Supply Piping

Return

Supply

Manual Shutoff Valve
with 1/8" NPT Plugged Tapping,
Accessible for Test GaugeConnection
(Field Supplied)

Drip Leg (Field Supplied)

Ground Joint Union (Field Supplied)

Condensate Drain

Access Panel to

Compressor and

Outdoor Fan

Access Panel to

Gas Valve and Burners

Access Panel to

Filter and Controls

Summary of Contents for MGE4-09-18

Page 1: ...installation of this appliance must conform to the requirements of the National Fire ProtectionAssociation the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadia...

Page 2: ...ice required Refer to Table 1 for the application limitations of the unit Location For information on wall sleeves and grille accessories see ACCESSORIES on page 17 The design is certified for thru th...

Page 3: ...on the unit and as tall as the unit IMPORTANT The unit must be installed with approved wall sleeve and grille accessories for safe operation Improper installa tions could result in property damage per...

Page 4: ...with appropriate wall sleeve accessories There is no minimum clearance required on locating the unit to an interior corner of a building If the unit is installed in a residential garage it must be loc...

Page 5: ...monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the common vent...

Page 6: ...all sleeve make sure that the proper louver kit is installed Due the high temperatures of the combustion products released from the gas vent MGE gas package units require the use of either an aluminum...

Page 7: ...unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America ACCA Check unit air supply outle...

Page 8: ...Low High MGE4 09 24 Low Medium Low Medium High Medium High High 650 630 610 580 550 500 470 435 390 370 670 640 575 520 460 750 690 645 575 490 795 740 680 616 535 945 900 860 810 775 1010 960 910 870...

Page 9: ...al Code CSA C22 2 Part 1 latest edition or local codes where they prevail Any alteration of internal wiring will void certification and warranty Units are factory wired for a 230 volt single phase pow...

Page 10: ...in the gas line outside the unit 5 above the floor or in accordance with any local codes The furnace must be isolated from the gas supply piping system by closing the individual manual shutoff valve d...

Page 11: ...dures Color coded insulated wires minimum 18AWG should be used to connect the thermostat to the unit The gas valve supplied with this furnace is rated at 1 2 psig maximum Any higher pressure may ruptu...

Page 12: ...er the pre purge time expires burners will light For Your Safety Read Before Lighting To Shut Down Unit 1 Turn off electrical power to unit 2 Depress and turn the gas valve knob to the OFF position se...

Page 13: ...r temporary or short periods of shutdown set the thermostat system switch to OFF For a prolonged period of shutdown set the thermostat system switch to OFF and turn off the electrical power supply and...

Page 14: ...ation Continuousoperationoftheairhandlingblowerwillbeobtained if the thermostat fan switch is set to ON With the thermostat fan switch set to AUTO the air handling blower will cycle corresponding with...

Page 15: ...5 To adjust the manifold pressure refer to previous section Checking andAdjusting Gas Input on page 13 For installations above 7500 feet refer to the National Fuel Gas Code Installation and Operation...

Page 16: ...tion control 3 Remove ignitor and flame sensor 4 Remove the four screws that mount the burner right side plate houses the ignitor flame sensing rod 5 Carefully remove the burner right side plate 6 Bur...

Page 17: ...2 6 Wall Sleeve Kit 6 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE8 1 ASLEEVE8 2 8 Wall Sleeve Kit 8 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE10 1 ASLEEVE10 2 10 Wall Sleeve Kit 10 Wall Sleeve Ki...

Page 18: ...V E E L S A 8 5 4 8 1 5 4 8 1 9 2 4 8 E V E E L S A 1 0 1 E V E E L S A 0 1 9 2 8 1 9 2 8 1 9 2 2 0 1 E V E E L S A 0 1 4 3 2 3 8 7 2 3 8 1 9 2 3 0 1 E V E E L S A 0 1 5 4 8 1 5 4 8 1 9 2 4 0 1 E V E...

Page 19: ...506326 01 Page 19 of 20 Issue 0941 Figure 10 Connection Diagram...

Page 20: ...Page 20 of 20 506326 01 Issue 0941 Figure 11 Schematic...

Reviews: