Magic-Pak MGE4-09-18 Installation And Maintenance Instructions Manual Download Page 6

Page 6  of  20

506326-01

Issue 0941

3.

Remove the 5/16" screw used to mount the vent pipe
assembly to the mounting bracket. Keep this screw.

4.

Five holes have been drilled into the vent extension (see
Figure 4). Four of those holes are provided so that the
vent can be extended the necessary length required for
the installation. The wall sleeve that is installed
determines which of these clearance holes should be
used. Using Table 2 and Figure 4, determine which
clearance hole should be used to position the vent
extension properly. Slide the vent extension outward and
line up the correct clearance hole on the vent extension
with the hole in the vent pipe and the hole in the mounting
bracket.

5.

Re-install the 5/16" screw that was removed in Step 3.
Thread the screw first through the clearance hole in the
mounting bracket, the proper clearance hole in the vent
extension, and into the engagement hole in the vent
pipe. The length of the vent pipe extension that extends
out of the cabinet should be as shown in Table 2.

6.

Position the vent pipe at the center of the steel insert
when using poly louvers.  The vent pipe should have a
slight downward slope to allow any moisture to drain
away from the unit as well as being centered on the
metal grate.

I

nstalling and Securing Unit to Wall Sleeve

Before installing and securing the unit to the wall sleeve,
make sure that the proper louver kit is installed. Due the
high temperatures of the combustion products released from
the gas vent, MGE gas package units require the use of
either an aluminum louver kit or special MGE polypropylene
louver kit (see 

ACCESSORIES

 on page 17).

1. Make sure the gaskets attached to the sleeve are not

damaged.

2.

Verify divider panel is positioned properly. Figure 5 shows
the correct position for 60" and 64" tall units (flange
pointing up). For 58" tall units, the divider panel should
be positioned so the flange points down.

1.

Access vent pipe at the side of the unit that will face the
outdoors.

2.

The vent pipe and vent pipe extension is located to the
right of the outdoor fan (see Figure 3).

Vent Pipe Installation

Determining the length of the vent pipe extension is
dependent upon which wall sleeve accessory is installed at
the job site for each particular installation.

For proper operation, the vent length must be correct for
the installation. The unit may not operate correctly with
inadequate vent length.

 CAUTION

Figure 3

Locating Vent Pipe and Extension

Mounting
Bracket

Vent Pipe

Outdoor Fan

Positioning Vent Pipe Extension

Figure 4

* The clearance holes are not marked on the actual

vent extension.

Outdoor Fan

0

Vent Extension

Clearance Holes*

Determining Hole Setting

Table 2

ASLEEVE12-1, 2, 3, 4

Hole
  #

Wall Sleeve Used

  Approximate
Length the Vent
  Extends from
   the Cabinet

ASLEEVE6-1, 2, 3, 4

ASLEEVE8-1, 2, 3, 4

ASLEEVE10-1, 2, 3, 4

ASLEEVE2-1,2

4

3

2

1

0

5.5 Inches

7.5 Inches

9.5 Inches

11.5 Inches

0 Inches

Summary of Contents for MGE4-09-18

Page 1: ...installation of this appliance must conform to the requirements of the National Fire ProtectionAssociation the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadia...

Page 2: ...ice required Refer to Table 1 for the application limitations of the unit Location For information on wall sleeves and grille accessories see ACCESSORIES on page 17 The design is certified for thru th...

Page 3: ...on the unit and as tall as the unit IMPORTANT The unit must be installed with approved wall sleeve and grille accessories for safe operation Improper installa tions could result in property damage per...

Page 4: ...with appropriate wall sleeve accessories There is no minimum clearance required on locating the unit to an interior corner of a building If the unit is installed in a residential garage it must be loc...

Page 5: ...monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the common vent...

Page 6: ...all sleeve make sure that the proper louver kit is installed Due the high temperatures of the combustion products released from the gas vent MGE gas package units require the use of either an aluminum...

Page 7: ...unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America ACCA Check unit air supply outle...

Page 8: ...Low High MGE4 09 24 Low Medium Low Medium High Medium High High 650 630 610 580 550 500 470 435 390 370 670 640 575 520 460 750 690 645 575 490 795 740 680 616 535 945 900 860 810 775 1010 960 910 870...

Page 9: ...al Code CSA C22 2 Part 1 latest edition or local codes where they prevail Any alteration of internal wiring will void certification and warranty Units are factory wired for a 230 volt single phase pow...

Page 10: ...in the gas line outside the unit 5 above the floor or in accordance with any local codes The furnace must be isolated from the gas supply piping system by closing the individual manual shutoff valve d...

Page 11: ...dures Color coded insulated wires minimum 18AWG should be used to connect the thermostat to the unit The gas valve supplied with this furnace is rated at 1 2 psig maximum Any higher pressure may ruptu...

Page 12: ...er the pre purge time expires burners will light For Your Safety Read Before Lighting To Shut Down Unit 1 Turn off electrical power to unit 2 Depress and turn the gas valve knob to the OFF position se...

Page 13: ...r temporary or short periods of shutdown set the thermostat system switch to OFF For a prolonged period of shutdown set the thermostat system switch to OFF and turn off the electrical power supply and...

Page 14: ...ation Continuousoperationoftheairhandlingblowerwillbeobtained if the thermostat fan switch is set to ON With the thermostat fan switch set to AUTO the air handling blower will cycle corresponding with...

Page 15: ...5 To adjust the manifold pressure refer to previous section Checking andAdjusting Gas Input on page 13 For installations above 7500 feet refer to the National Fuel Gas Code Installation and Operation...

Page 16: ...tion control 3 Remove ignitor and flame sensor 4 Remove the four screws that mount the burner right side plate houses the ignitor flame sensing rod 5 Carefully remove the burner right side plate 6 Bur...

Page 17: ...2 6 Wall Sleeve Kit 6 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE8 1 ASLEEVE8 2 8 Wall Sleeve Kit 8 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE10 1 ASLEEVE10 2 10 Wall Sleeve Kit 10 Wall Sleeve Ki...

Page 18: ...V E E L S A 8 5 4 8 1 5 4 8 1 9 2 4 8 E V E E L S A 1 0 1 E V E E L S A 0 1 9 2 8 1 9 2 8 1 9 2 2 0 1 E V E E L S A 0 1 4 3 2 3 8 7 2 3 8 1 9 2 3 0 1 E V E E L S A 0 1 5 4 8 1 5 4 8 1 9 2 4 0 1 E V E...

Page 19: ...506326 01 Page 19 of 20 Issue 0941 Figure 10 Connection Diagram...

Page 20: ...Page 20 of 20 506326 01 Issue 0941 Figure 11 Schematic...

Reviews: