background image

Page 4  of  20

506326-01

Issue 0941

Wall Sleeve and Louver Grille Installation

Refer to installation instructions included with the wall sleeve
kit and the louver grille kit along with Figure 2 for guidance
in assembling and installing the wall sleeve and louver grille.

The outside of the unit may be flush with the face of the
exterior wall, and it should not be obstructed with trees,
landscape materials, or building structure. Unit can be
installed recessed with appropriate wall sleeve accessories.
There is no minimum clearance required on locating the
unit to an interior corner of a building.

If the unit is installed in a residential garage, it must be located
or protected to avoid physical damage by vehicles. The unit
must be installed so that no electrical components are
exposed to water.  If drains are exposed to temperatures
below freezing they must be protected.

This unit must be installed level to allow for proper
drainage of the unit base pan and indoor drain pan.

 CAUTION

Figure 2

Wall Sleeve and Louver Kit Installed

NOTE:

  Platform must be constructed so that it is level with sill plate of wall opening.

Summary of Contents for MGE4-09-18

Page 1: ...installation of this appliance must conform to the requirements of the National Fire ProtectionAssociation the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadia...

Page 2: ...ice required Refer to Table 1 for the application limitations of the unit Location For information on wall sleeves and grille accessories see ACCESSORIES on page 17 The design is certified for thru th...

Page 3: ...on the unit and as tall as the unit IMPORTANT The unit must be installed with approved wall sleeve and grille accessories for safe operation Improper installa tions could result in property damage per...

Page 4: ...with appropriate wall sleeve accessories There is no minimum clearance required on locating the unit to an interior corner of a building If the unit is installed in a residential garage it must be loc...

Page 5: ...monoxide poisoning or death The following steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the common vent...

Page 6: ...all sleeve make sure that the proper louver kit is installed Due the high temperatures of the combustion products released from the gas vent MGE gas package units require the use of either an aluminum...

Page 7: ...unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America ACCA Check unit air supply outle...

Page 8: ...Low High MGE4 09 24 Low Medium Low Medium High Medium High High 650 630 610 580 550 500 470 435 390 370 670 640 575 520 460 750 690 645 575 490 795 740 680 616 535 945 900 860 810 775 1010 960 910 870...

Page 9: ...al Code CSA C22 2 Part 1 latest edition or local codes where they prevail Any alteration of internal wiring will void certification and warranty Units are factory wired for a 230 volt single phase pow...

Page 10: ...in the gas line outside the unit 5 above the floor or in accordance with any local codes The furnace must be isolated from the gas supply piping system by closing the individual manual shutoff valve d...

Page 11: ...dures Color coded insulated wires minimum 18AWG should be used to connect the thermostat to the unit The gas valve supplied with this furnace is rated at 1 2 psig maximum Any higher pressure may ruptu...

Page 12: ...er the pre purge time expires burners will light For Your Safety Read Before Lighting To Shut Down Unit 1 Turn off electrical power to unit 2 Depress and turn the gas valve knob to the OFF position se...

Page 13: ...r temporary or short periods of shutdown set the thermostat system switch to OFF For a prolonged period of shutdown set the thermostat system switch to OFF and turn off the electrical power supply and...

Page 14: ...ation Continuousoperationoftheairhandlingblowerwillbeobtained if the thermostat fan switch is set to ON With the thermostat fan switch set to AUTO the air handling blower will cycle corresponding with...

Page 15: ...5 To adjust the manifold pressure refer to previous section Checking andAdjusting Gas Input on page 13 For installations above 7500 feet refer to the National Fuel Gas Code Installation and Operation...

Page 16: ...tion control 3 Remove ignitor and flame sensor 4 Remove the four screws that mount the burner right side plate houses the ignitor flame sensing rod 5 Carefully remove the burner right side plate 6 Bur...

Page 17: ...2 6 Wall Sleeve Kit 6 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE8 1 ASLEEVE8 2 8 Wall Sleeve Kit 8 Wall Sleeve Kit MGE4 10 30 MGE4 09 36 ASLEEVE10 1 ASLEEVE10 2 10 Wall Sleeve Kit 10 Wall Sleeve Ki...

Page 18: ...V E E L S A 8 5 4 8 1 5 4 8 1 9 2 4 8 E V E E L S A 1 0 1 E V E E L S A 0 1 9 2 8 1 9 2 8 1 9 2 2 0 1 E V E E L S A 0 1 4 3 2 3 8 7 2 3 8 1 9 2 3 0 1 E V E E L S A 0 1 5 4 8 1 5 4 8 1 9 2 4 0 1 E V E...

Page 19: ...506326 01 Page 19 of 20 Issue 0941 Figure 10 Connection Diagram...

Page 20: ...Page 20 of 20 506326 01 Issue 0941 Figure 11 Schematic...