035-000029-001
Page 59
HHA IOM 1.4 10/11/2021
Model HHA
Critical Environment AHU
UV Light Option
Features & Benefits
UVC Light –technology with decades long anti-microbial track record
Includes safety interlock switches at each door for operator safety
Details
Factory installed & tested.
Located after first coil, above
drain pan
Takes up 4-rows of coil space
(sizes 04-25) or 2-rows of coil
space (sizes 30 & 40)
Service of lamp and ballast
through separate access door
opposite coil connections
Specifications:
The UV light option has an emitter specified to produce germicidal
UVC output at 253.7 nm wavelength. The single-ended UVC Emitter
is designed to maximize photon production, irradiance and reliability
in cold air streams of 35 - 140ºF, 99% RH and up to 2000 fpm. It
produces no ozone or other secondary contaminants.
The power supply complies with ANSI/UL Standards 153, 1598
and 1995 and CSA standards.