035-000029-001
Page 48
HHA IOM 1.4 10/11/2021
Table 3—VFD Parameters—Control (digit 17) Option D
(Constant CFM control)
SERVICE-VFD Parameters—Cont’d
Parameter Index
Parameter Function
Setting
1611
Parameter View
3 (Long View)
9902
Application Macro
1 (HVAC Default)
9905
Motor Nom Voltage
230 or 460 (see Nameplate)
9906
Motor Nominal Current
SEE MOTOR TABLE (PG 49)
9908
Motor Nominal Speed
3500 (HHA04-25); 1750 (HHA30-40)
1001
Start/Stop Command
1 (DI1)
1002
EXT 2 Comands
1 (DI1)
1003
Motor Direction
1 (Forward)
1102
EXT 1 - EXT 2 SEL
EXT 2
1104
Min Frequency
10 Hz
1105
Max Ref Frequency
SEE MOTOR TABLE (PG 49)
1103
REF1 Select
2(AI2)
1106
REF2 Select
19(PID1Out)
1201
Constant Speed Selection
0 (No Constant Speed)
1301
AI-1 Minimum
0.2
1302
AI-1 Maximum
1
1601
run enable
1 (DI1)
1608
Start Enable
1 (DI1)
1609
Start Enable 2
1 (DI1)
1610
Display Alarms
1 (Yes)
2003
Max Motor Current
SEE MOTOR TABLE (PG 49)
2008
Maximum Output drive frequency
SEE MOTOR TABLE (PG 49)
2202
Acceleration Time
5s
2203
Decel Time
5s
2606
Switching Frequency
16 kHz
3404
OUTPUT 1 DISPLAY FORM
9 (Direct)
3408
SIGNAL 2 PARAM
130 (PID 1 FBK)
3411
OUTPUT 2 DSP FORM
6 (2 DEC)
3412
OUTPUT 2 DSP UNIT
58 (in H20)
3415
OUTPUT 3 PARAMETER
0128 (PID SETPOINT)
3418
OUTPUT 3 DISPLAY FORM
6 (2 DEC)
3419
OUTPUT 3 UNITS
58 (in H20)
(Parameters continued on Page 49)
Summary of Contents for HHA Series
Page 2: ...035 000029 001 Page 2 HHA IOM 1 4 10 11 2021 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 55: ...035 000029 001 Page 55 HHA IOM 1 4 10 11 2021...
Page 56: ...035 000029 001 Page 56 HHA IOM 1 4 10 11 2021...
Page 57: ...035 000029 001 Page 57 HHA IOM 1 4 10 11 2021 B...
Page 58: ...035 000029 001 Page 58 HHA IOM 1 4 10 11 2021 D...
Page 63: ...035 000029 001 Page 63 HHA IOM 1 4 10 11 2021 THIS PAGE INTENTIONALLY LEFT BLANK...