Figure B-12 Sensor Type
↑
Alarm Level - set level if needed, 0 = disable
S e n s o r 0 1 C O
A l a r m : 2 0 0 p p m
Figure B-13 Sensor Alarm Level
↑
Warning Level - set level if needed
S e n s o r 0 1 C O
W a r n i n G : _ 5 0 p p m
Figure B-14 Sensor Warning Level
↑
Sensor Range - default range is in system
S e n s o r 0 1 C O
R a n g e : 2 0 0 p p m
Figure B-15 Sensor Range
↑
Next Sensor - complete for all sensor channels
9.3
Configure Relays, Horn & Strobe Submenu
9.3.1
4.13.4 Configure Relays, Horn & Strobe Submenu
Press Menu to display Hardware Summary
↑
x 3 Configure Relays
→
Relay 1
R e l a y 1 N o r m . O f f
D e l a y O N , M i n . O n
Figure B-16 Relay Summary
Default – Normally Off
R e l a y 1 N o r m . O f f
M o d e : 2
Figure B-17 Relay Mode
Default - Delay – 1 Minute
R e l a y 1 D e l a y O n
( m m : s s ) 0 1 : 0 0
Figure B-18 Turn on Delay
Default - Minimum Runtime - 1 Minute
R e l a y 1 M i n . O n