Macurco DVP-120C Manual
REV – 1.0
[34-8708-4770-8 ]
42
|
P a g e
The default range values for the sensor are:
Description Carbon
Monoxide
Nitrogen
Dioxide
Rang
200 ppm
20 ppm
Table 4-7 Default Range
4.13.4
Configure Relays, Horn & Strobe Submenu
There is a list of parameters for each relay in the system. The left and right cursor keys can be used to move from
one relay, horn or strobe to another and the up and down keys will scroll through the parameters for the particular
relay, horn or strobe.
4.13.4.1
Relay Summary
R e l a y 1 N o r m . O f f
D e l a y O n , M i n . O n
Figure 4-58 Relay Summary
This display example shows that Relay 1 is configured to operate Normally Off, with a turn-on delay and a minimum
on time.
Notice that the relay number, 1 in this example, is underlined. This indicates that the digit keys can be used to jump
to a particular relay, horn or strobe. The relays are numbers 1, 2 and 3; the horn is number 4 and the strobe is 5.
4.13.4.2
Relay Mode
R e l a y 1 N o r m . O f f
M o d e : 2
Figure 4-59 Relay Mode
This display example shows that relay 1 is configured to operate in the Normally Off mode. The relay modes are:
•
1
ALARM
•
2
Normally Off (default)
•
3
Normally On
Relay mode 1 is a special case. This mode is only available on relay 1 and dedicates the relay to function as an alarm
signal to a subsequent alarm or monitoring panel. This mode forces the relay to Normally Off mode with no turn on
delay or minimum on time. See Section
for more detail regarding alarms.
Fail Safe operation can be implemented by configuring a relay to operate Normally On, and wiring the circuit using
the NC (normally closed) contact. In this way, if the control panel loses power the relay will turn on the controlled
device if it still has power.
4.13.4.3
Relay Turn on Delay
R e l a y 1 D e l a y O n
( m m : s s ) 0 1 : 0 0