Macurco
TM
DVP-1200 Manual
REV – 1.3.1
[34-8708-4770-7 ]
54
|
P a g e
Description
BACnet Object Type
BACnet Object Instance
Rising
Analog value
54+(N-1)*68
Falling
Analog value
55+(N-1)*68
Alarm2
Analog value
56+(N-1)*68
Warning2
Analog value
57+(N-1)*68
Rising2
Analog value
58+(N-1)*68
Falling 2
Analog value
59+(N-1)*68
mode
Analog value
60+(N-1)*68
Gas
sensor
[CO
2
]
type
Analog value
61+(N-1)*68
Eng. unit
Analog value
62+(N-1)*68
range
Analog value
63+(N-1)*68
Alarm
Analog value
64+(N-1)*68
Warning
Analog value
65+(N-1)*68
Rising
Analog value
66+(N-1)*68
Falling
Analog value
67+(N-1)*68
Table 5-3 – BACnet Objects for Group Settings of all Zone
2.
Readings and Type for all detectors
Each sensor addresses from 1 to 192 has two BACnet Objects (one for sensor reading and one for sensor type referred as
group). Table 5-4 shows the BACnet objects and corresponding object instance. N in Table 4 refers to the sensor address.
E.g. to retrieve sensor reading for address 16, corresponding object instance is 553 + (16-1)*2 = 583.
If a sensor address is not detected by the panel, then corresponding BACnet object reading and group value will be 65535
and 0, respectively.
Note
: If the value of sensor reading BACnet object is outside the range of detection of the sensor then the reading is not
reliable and cause for unreliable reading must be investigated. Refer to Table 4-2 or sensor manual for information on range
of detection.
Description
BACnet Object Type
BACnet Object
Instance
Notes
Sensors[N]
Where
N is from 1 to 192
reading
Analog value
553+(N-1)*2
e.g. To retrieve sensor #
16 reading, use
553+(16-1)*2 = 583
type
Analog value
553+(N-1)*2+1
Table 5-4 – BACnet Object for Detector Reading
3.
Zone Configurations (Types of detectors assigned, Horn/Strobe Assigned, Relay Assigned, Analog Output Assigned,
Quorum for Voting Mode) for all Zones
Table 5-6 shows the BACnet Objects representing zone configuration for each zone. N in Table 5-6 refers Zone number.
When binary output is set to 1 (or active), it means that the corresponding DVP-1200 output (Horn/Strobe, Relay) is
configured or assigned to that zone, or in case of the group[X] means that the sensor of type X (Table 5-1 lists the valid
values of type i.e. value of X) is added to that zone.
If any of the three analog outputs are assigned to the zone, then object “analog output” for corresponding zone will have
the analog output number (valid values are 1,2 and 3). If the zone does not have any analog (or 4-20mA) output assigned,
then “analog output” will have value 0.