Macurco
TM
DVP-1200 Manual
REV – 1.3.1
[34-8708-4770-7 ]
49
|
P a g e
Figure 4-53 –
Disable: No
- If any sensor is disabled, the panel will not take the sensor readings into consideration for Zone Outputs activation,
panel fault conditions, etc. This is like a virtual delete.
When a sensor previously disabled is enabled back, then all the functionality related to the sensor is resumed back, i.e. sensor
readings will be taken into consideration for Zone Outputs activation, panel fault conditions, etc.
This option allows the user to disconnect a sensor for repair or replacement without any trouble or error at the panel. For
example, to replace a sensor, first disable that specific sensor in the panel. Then, disconnect it from the system and replace it
with the new unit (of same type). Lastly, return to the VIEW SENSORS menu and enable the sensor. Using this method, all
previous sensor configurations will be retained so it will not be necessary to reconfigure the sensor.
Delete
– This will delete the sensor from the panel and from all the zone to which the sensor is added.
If the sensor is connected to the panel even after deleting it, then the panel must discover the sensor again. However, it will be
like a new sensor discovery. Therefore, the sensor will not be added to any zones.
Note: When replacing a sensor (already registered with DVP-1200) with a sensor of different type but same address(e.g. CO
sensor with address 17 replaced with NO2 sensor with address 17) then it is recommended to perform a Delete operation for
corresponding sensor address, after sensor replacement is complete, and verify correct sensor type is displayed for
corresponding sensor address.
Type:
- Displays the sensor type. See Table 4-2 for a definition of each type.
The bottom box of the display shows the current gas reading of the detector. It also lists any zones the detector is part of. E.g. In
following example, Sensor 1 is CO Sensor (Type: 1) reading 0ppm and is currently assigned to Zone 1.