Operation Instruction of S900 E Series Inverter
·
89
·
When fault restart function is valid, motor may start suddenly, so
when this function is used, please pay attention to safety.
P422
Over torque action Default 0
Range
0-3
unit
1
Settings
0: Inverter start detecting over torque only in
constant speed, inverter continues operation
during over torque
1: Inverter start detecting over torque only in
constant speed, inverter stop during over torque
2: Inverter always detecting over torque, inverter
continues operation during over torque
3: Inverter always detecting over torque, inverter
stop during over torque
P423
Over torque detection level Default 0
Range
0-200%
Minimum
1
P424
Over torque detection time Default 0
Range
0-200s
Minimum
1
When output current of inverter exceeds setting value of P423, inverter
start calculate the over torque time. When the duration exceeds half
of setting value of P424, inverter output pre-alarm signal. Inverter
continues output until the over torque time exceeds P424 setting, and
then inverter protects and output alarm signal.
If P423=0. over torque detection is invalid, and 100% is inverter
rated current.
P423
Torque curve
P424
2
Running state
Overtorque
alarm