Chapter 7 Detailed Explanations of Functional Parameters
0: Invalid
During deceleration, the DC-bus voltage may increase, when over-
voltage prevention selection is invalid, inverter may trip for over
voltage.
1: Valid
During deceleration, when DC-bus voltage reaches the setting
value, inverter will stop the deceleration procedure. When DC-
bus voltage returns to allowable value, inverter will resume the
deceleration.
Output frequency
DC voltage
Voltage
directrix
Shutdown
command
P412
Automatic voltage regulation selection Default value 1
Range
0-2
Unit
1
Settings
0: Invalid
1: Valid
2: Invalid when decelerating
If the input voltage is not stable, temperature of the machinery will
increase, insulation may be damaged, and output torque will be
instable.
0: Invalid
Select automatic voltage regulation to be invalid, inverter output
voltage fluctuates.
1: Automatic voltage regulation is valid.
Automatic voltage regulation function is selected, and under the
condition that input electric source is instable, inverter output stable
voltage automatically.