102
·
Operation Instruction of S900 E Series Inverter
·
103
·
figured out (
△
FHz) every time. While frequency increment is more than
value of P610 in maximum of frequency increment, P610 will work.
P611
PID standby frequency Initial value : 0.00
Setting range
0.00 – 120.00HZ
Unit
0.01
P612
PID standby duration Initial value : 10.0
Setting range
0.0 – 200.0
Unit
0.1
P613
PID wake-up value Initial
value: 0.0%
Setting range
0.0 – 100%
P611 PID standby frequency.
P611 must reach minimum frequency in PID standby. When running
frequency is less than value of P610 standby duration will begin
counting.
P612 PID standby duration.
When running duration of inverter is more than standby frequency
the value (standby duration) of P612, the inverter will be standby.
Then stop output, and disconnect with PID, but monitor the
feedback of P613 PID.
P613: PID wake-up value.
When the inverter detects that feedback value less than wake-up value
(P613), PID function will be taken action, and then inverter will start.
P612
Target value
P614 Awaking value
P612 Dormancy
frequency
Operating frequency
Feedback curve
Dormancy time
Shutdown PID closes